INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201691 Rev 1 www.powerware.com

A-34

Table Q. MBC Customer Interface Connections

CUSTJ4 Terminal

Name

Description

1

Building Alarm 2

P

bl UPS l

A ti

t d b

t d

t

t l

2

Building Alarm 2 Return

Programmable UPS alarm. Activated by a remote dry contact closure.

3

Building Alarm 3

P

bl UPS l

A ti

t d b

t d

t

t l

4

Building Alarm 3 Return

Programmable UPS alarm. Activated by a remote dry contact closure.

5

Building Alarm 4

P

bl UPS l

A ti

t d b

t d

t

t l

6

Building Alarm 4 Return

Programmable UPS alarm. Activated by a remote dry contact closure.

7

Building Alarm 5

P

bl UPS l

A ti

t d b

t d

t

t l

8

Building Alarm 5 Return

Programmable UPS alarm. Activated by a remote dry contact closure.

9

Not Used

10

Not Used

CUSTJ2 Terminal

Name

Description

1

Relay 1 NC

2

Relay 1 Common

General purpose normally-open and normally-closed relay contacts.

3

Relay 1 NO

p p

y p

y

y

4

Building Alarm 1

P

bl UPS l

A ti

t d b

t d

t

t l

5

Building Alarm 1 Return

Programmable UPS alarm. Activated by a remote dry contact closure.

6

Relay 2 NC

7

Relay 2 Common

General purpose normally-open and normally-closed relay contacts.

8

Relay 2 NO

p p

y p

y

y

9

Not Used

10

Not Used

CUSTTB Terminal

Name

Description

1

CB3 - Aux #2

Ci

it b

k

CB3

ili

t

t

2

CB3 - Aux #2*

Circuit breaker CB3 auxiliary contact.

3

Not Used

4

CB4- Aux #2

Ci

it b

k

CB4

ili

t

t

5

CB4- Aux #2*

Circuit breaker CB4 auxiliary contact.

6

Not Used

7

Not Used

8

Not Used

9

REPO

D

t

t

d t

ti

t REPO f UPS

10

REPO Common

Dry contact used to activate REPO of UPS.