INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201691 Rev 1 www.powerware.com

A-19

14. External overcurrent protection is not provided by this product, but is required

by codes. See Table E through Table G starting on page A-13 for wiring
requirements. If an output lockable disconnect is required, it is to be supplied
by designated personnel.

15. Table K lists the maximum rating for continuous duty rated input circuit

breakers.

C A U T I O N

To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current
ratings from Table K according to the NEC, ANSI/NFPA 70.

Table K. Maximum Input Circuit Breaker Ratings

UPS M d l

Input Voltage Rating

UPS Model

400V

480V

600V

PW9315-625/400
PW9315-625/450

1000A

N/A

N/A

PW9315-625/500
PW9315-625/562

1200A

N/A

N/A

PW9315-750/500
PW9315-750/562

N/A

1000A

800A

PW9315-750/600
PW9315-750/675

N/A

1200A

1000A

16. Source protection for the AC input should be treated as if you were supplying a

750 kVA three-phase transformer, to allow for inrush current.

17. The input breaker (CB1) has a trip rating of 1200 amps AT and a standard

ampere interrupting capacity (AIC) of 65,000 in symmetrical RMS amps. An
optional 100,000 AIC breaker is available.

18. The input and bypass three-phase feeds should be symmetrical about ground,

due to the existence of voltage surge protection devices.

19. The line-to-line unbalanced output capability of the UPS is limited only by the

full load per phase current values for AC output to critical load shown in
Table E through Table G. The recommended line-to-line load unbalance is 50%
or less.

20. Output overcurrent protection and output disconnect switch are to be provided

by the user. Table L lists the maximum rating for continuous duty rated output
circuit breakers satisfying the criteria for both.