USING FEATURES AND OPTIONS

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201691 Rev 1 www.powerware.com

10-5

10.5

Optional Supervisory Contact Module

An optional Supervisory Contact Module (SCM) establishes an interface between the
Parallel Capacity/Redundant system manufacturer’s equipment and the customer’s
monitor. This interface allows the customer to monitor operational status of the
Parallel Capacity/Redundant system equipment. Figure 10-3 shows the SCM, input
connections on TB1, and output connections on TB2.

TB2

Figure 10-3. SCM

The SCM provides signals for the following indications:

SYSTEM NORMAL

TB2-1 through TB2-3

NO REDUNDANCY

TB2-4 through TB2-6

ON GENERATOR

TB2-7 through TB2-9

BYPASS NOT AVAILABLE

TB2-10 through TB2-12

ON BATTERY

TB2-13 through TB2-15

UPS ALARM

TB2-16 through TB2-18

ON BYPASS

TB2-19 through TB2-21

SHUTDOWN IMMINENT

TB2-22 through TB2-24