A-17

10. Per NEC, Article 300-20(a), all three-phase conductors must be run in the same

conduit. If a neutral and/or ground is used, it must be run in the same conduit
as the phase conductors.

11. Conduit is sized to accommodate one neutral conductor the same size as the

phase conductor (if applicable) and one 2/0 ground conductor.

12. Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW,

RHW-2, TW, THW, THHW, THW-2.

Table I. Power Cable Conduit Requirements

UPS Model

Voltage

Terminal

Number of Wires

in Conduit

Minimum Conduit

Trade Size

Number of

Conduits

AC Input to UPS (A, B, C, Ground)

5

3.5”

3

PW9315 750/600

600

AC Input to MBC (A, B, C, Ground)

4

3”

3

PW9315-750/600
PW9315-750/675

Output (A, B, C, Neutral, Ground)

4

3”

3

PW9315 750/675

480

Battery

(Positive, Negative, Ground)

4

3.5”

2

AC Input to UPS (A, B, C, Ground)

5

4”

3

PW9315 750/600

480

AC Input to MBC (A, B, C, Ground)

6

3.5”

3

PW9315-750/600
PW9315-750/675

Output (A, B, C, Neutral, Ground)

6

3.5”

3

PW9315 750/675

480

Battery

(Positive, Negative, Ground)

4

3.5”

2

AC Input to UPS (A, B, C, Ground)

5

3”

3

PW9315 750/500

600

AC Input to MBC (A, B, C, Ground)

5

3”

3

PW9315-750/500
PW9315-750/562

Output (A, B, C, Neutral, Ground)

5

3”

3

PW9315 750/562

480

Battery

(Positive, Negative, Ground)

4

3”

2

AC Input to UPS (A, B, C, Ground)

5

3.5”

3

PW9315 750/500

480

AC Input to MBC (A, B, C, Ground)

4

3”

3

PW9315-750/500
PW9315-750/562

Output (A, B, C, Neutral, Ground)

4

3”

3

PW9315 750/562

480

Battery

(Positive, Negative, Ground)

4

3”

2

AC Input to UPS (A, B, C, Ground)

4

3.5”

4

PW9315 625/500

400

AC Input to MBC (A, B, C, Ground)

5

3.5”

3

PW9315-625/500
PW9315-625/562

Output (A, B, C, Neutral, Ground)

5

3.5”

3

PW9315 625/562

480

Battery

(Positive, Negative, Ground)

4

3”

2

AC Input to UPS (A, B, C, Ground)

5

3”

3

PW9315 625/400

400

AC Input to MBC (A, B, C, Ground)

5

3”

3

PW9315-625/400
PW9315-625/450

Output (A, B, C, Neutral, Ground)

5

3”

3

PW9315 625/450

480

Battery

(Positive, Negative, Ground)

6

3.5”

1