Eaton POWERWARE 9315 User Manual

Page 126

Advertising
background image

INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201691 Rev 1 www.powerware.com

A-16

9.

Terminals E1 through E12 are 2-hole bus bar mountings for standard NEMA
2-hole barrel lugs. See Table H for power cable terminations, Table I for conduit
requirements, and Table J for recommended installation parts and tools not
supplied by Eaton. Section A.4 shows the location of the power cable
terminals inside the UPS.

Table H. Powerware 9315 UPS (500–750 kVA) Cabinet Power Cable Terminations

Terminal Function

Terminal

Function

Size of Pressure Termination

Tightening Torque

Nm (lb in)

Bolt Size

AC Input to UPS Rectifier
(CB1 I

t)

E1

Phase A

4 - 2 bolt mounting

76 (56)

1/2”

(CB1 Input)

E2

Phase B

4 - 2 bolt mounting

76 (56)

1/2”

E3

Phase C

4 - 2 bolt mounting

76 (56)

1/2”

AC Input to MBC (UPS Bypass)

E6

Phase A

4 - 2 bolt mounting

76 (56)

1/2”

E7

Phase B

4 - 2 bolt mounting

76 (56)

1/2”

E8

Phase C

4 - 2 bolt mounting

76 (56)

1/2”

AC Output from Inverter to MBC or
SBM

E9

Phase A

4 - 2 bolt mounting

76 (56)

1/2”

SBM

E10

Phase B

4 - 2 bolt mounting

76 (56)

1/2”

E11

Phase C

4 - 2 bolt mounting

76 (56)

1/2”

E12

Neutral

4 - 2 bolt mounting

76 (56)

1/2”

AC Input to MBC from Inverter

E9

Phase A

4 - 1 bolt mounting

76 (56)

1/2”

E10

Phase B

4 - 1 bolt mounting

76 (56)

1/2”

E11

Phase C

4 - 1 bolt mounting

76 (56)

1/2”

E12

Neutral

4 - 1 bolt mounting

76 (56)

1/2”

AC Output to Critical Load from MBC

E9

Phase A

12 - 2 bolt mounting

76 (56)

1/2”

E10

Phase B

4 - 2 bolt mounting

76 (56)

1/2”

E11

Phase C

4 - 2 bolt mounting

76 (56)

1/2”

DC Input from Battery to UPS

E4

Positive

6 - 2 bolt mounting

76 (56)

1/2”

E5

Negative

6 - 2 bolt mounting

76 (56)

1/2”

DC Link Output from Rectifier to
I

t

(+)

DC Link (+)

4 - 1 bolt mounting

20 (15)

Supplied

Inverter

(–)

DC Link (–)

4 - 1 bolt mounting

20 (15)

Supplied

DC Link Input to Inverter from
R

tifi

Inverter (+)

DC Link (+)

6 - 1 bolt mounting

20 (15)

Supplied

Rectifier

Inverter (–)

DC Link (–)

6 - 1 bolt mounting

20 (15)

Supplied

Neutral, Output

E12

Neutral

12 - 2 bolt mounting

76 (56)

1/2”

Customer Ground

Ground

Ground

8 - 2 bolt mounting

76 (56)

1/2”

NOTE Customer ground, size 2/0, can be run in any conduit listed in Table I on page A-17.