INSTALLING A REMOTE BATTERY DISCONNECT

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201691 Rev 1 www.powerware.com

4-2

S

Nominal voltages listed in this chapter are for a lead-acid batteries rated per NEC at
2.00 Vdc per cell.

S

Battery strings must be installed according to all applicable codes and regulations,
including NEC, Article 480.

S

The UPS to battery cable should be sized for a total maximum voltage drop
of 1% nominal DC Link voltage at maximum current.

S

Table 4-1 details the power cable terminations.

S

The remote battery disconnect weighs approximately 60.3 kg (133 lb).
It has an ampere interrupting capacity (AIC) of 100,000 at 500 Vdc.

Table 4-1. Remote Battery Disconnect Power Terminations

Number and Type of Accessories Permitted

Terminal

Terminal Function

Size of Termination

Tightening Torque

Nm (lb ft)

Bolt Size

E4 (+)

UPS Battery Input (+)

See Table H on page A-16

E5 (–)

UPS Battery Input (–)

See Table H on page A-16

Breaker (+)

Battery Disconnect (+)

8 – 1 Bolt Mounting

Bus Bar

76 (56)

1/2”

Breaker (–)

Battery Disconnect (–)

8 – 1 Bolt Mounting

Bus Bar

76 (56)

1/2”

Breaker (jumper)

Battery Disconnect

(jumper)

8 – 1 Bolt Mounting

Bus Bar

76 (56)

1/2”

Table 4-2. Remote Battery Disconnect Circuit Breaker Ratings

UPS Model

Circuit Breaker Rating

DC Voltage

9315-750/500

1600

480

9315-750/625

2000

480

9315-750/750

2500

480