INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201691 Rev 1 www.powerware.com

A-21

28. A battery disconnect switch is recommended, and may be required by NEC or

local codes when batteries are remotely located. The battery disconnect
switch may be supplied as an accessory, and should be installed between
battery and UPS.

29. If the conductors used for DC input from the battery string to the UPS are

those provided by the UPS manufacturer, and the UPS and battery string are
manufactured by the same supplier, then it is acceptable if they do not meet
the noted minimum conductor sizes.

30. The UPS DC disconnect trip signal from CB2TB, points 9 and 10 (shunt trip)

must be connected to the DC source disconnect device.

S.T. RTN-24 VDC

CB2 AUX #1

CNT-120 VAC

NOT USED

NOT USED

NOT USED

CB2TB

ST

BATTERY

DISCONNECT

CB2 AUX #1

S.T. RTN-24 VDC

CB2 CLS-120 VAC

CNT-NEUT

Figure A-11. CB2TB to DC Source Disconnect Device