Eaton POWERWARE 9315 User Manual

Page 124

Advertising
background image

INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201691 Rev 1 www.powerware.com

A-14

Table F. Input/Output Ratings and External Wiring Requirements (PW9315-700/500 and PW9315-750/562)

Basic Unit Rating

PW9315 750/500

0 8 L

i

F L

d

Units

Rating 50/60 Hz

PW9315-750/500 at 0.8 Lagging pF Load
PW9315-750/562 at 0.9 Lagging pF Load

kVA/kW

625/500

625/500

625/562

625/562

Input and Output Voltage

Volts

480

600

480

600

AC Input to UPS Rectifier (0.95 Min. pF)

(3) Phases, (1) Neutral, (1) Ground

Amps*

951

761

984

787

Minimum Conductor Size
Number per Phase
* Maximum amps includes full load current plus
battery recharge current

A

AWG or kcmil

(each)

400

(4)

350

(4)

500

(4)

350

(4)

AC Input to MBC (UPS Bypass)

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

B

Amps

752

601

752

601

Minimum Conductor Size
Number per Phase

B

AWG or kcmil

(each)

500

(3)

350

(3)

500

(3)

350

(3)

DC Input from Battery to UPS

(1) Positive, (1) Negative

C

Vdc

Amps @ (2.0V/cell)

480

1096

480

1096

480

1234

480

1234

Minimum Conductor Size
Number per Pole

C

AWG or kcmil

(each)

400

(4)

400

(4)

500

(4)

500

(4)

AC Output to Optional SBM

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

E

Amps

752

601

752

601

Minimum Conductor Size
Number per Phase

E

AWG or kcmil

(each)

500

(3)

350

(3)

500

(3)

350

(3)

AC Output to Critical Load

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

D

Amps

752

601

752

601

Minimum Conductor Size
Number per Phase

D

AWG or kcmil

(each)

500

(3)

350

(3)

500

(3)

350

(3)

NOTE

Callout letters A, B, C, D, and E map to Figure A-8.