INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201691 Rev 1 www.powerware.com

A-13

Table E. Input/Output Ratings and External Wiring Requirements (PW9315-625/400, PW9315-625/450, PW9315-625/500, and PW9315-625/562)

Basic Unit Rating

PW9315 625/400

d PW9315 625/500

0 8 L

i

F L

d

Units

Rating 50/60 Hz

PW9315-625/400 and PW9315-625/500 at 0.8 Lagging pF Load
PW9315-625/450 and PW9325-625/562 at 0.9 Lagging pF Load

kVA/kW

500/400

500/450

625/500

625/562

Input and Output Voltage

Volts

400

400

400

400

AC Input to UPS Rectifier (0.95 Min. pF)

(3) Phases, (1) Neutral, (1) Ground

Amps*

880

910

1100

1138

Minimum Conductor Size
Number per Phase
* Maximum amps includes full load current plus
battery recharge current

A

AWG or kcmil

(each)

350

(4)

400

(4)

600

(4)

700

(4)

AC Input to MBC (UPS Bypass)

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

B

Amps

722

722

902

902

Minimum Conductor Size
Number per Phase

B

AWG or kcmil

(each)

300

(4)

300

(4)

500

(4)

500

(4)

DC Input from Battery to UPS

(1) Positive, (1) Negative

C

Vdc

Amps @ (2.0V/cell)

480
877

480
987

480

1097

480

1234

Minimum Conductor Size
Number per Pole

C

AWG or kcmil

(each)

400

(3)

400

(3)

400

(4)

500

(4)

AC Output to Optional SBM

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

E

Amps

722

722

902

902

Minimum Conductor Size
Number per Phase

E

AWG or kcmil

(each)

300

(4)

300

(4)

500

(4)

500

(4)

AC Output to Critical Load

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

D

Amps

722

722

902

902

Minimum Conductor Size
Number per Phase

D

AWG or kcmil

(each)

300

(4)

300

(4)

500

(4)

500

(4)

NOTE

Callout letters A, B, C, D, and E map to Figure A-8.