A.9 scm dimensions and mounting details – Eaton POWERWARE 9315 User Manual

Page 151

Advertising
background image

INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201691 Rev 1 www.powerware.com

A-41

A.9

SCM Dimensions and Mounting Details

41.1

DIMENSIONS ARE IN MILLIMETERS [INCHES]

100.1
[3.94]

74.7

[2.94]

171.5
[6.75]

25.4

[1.00]

KNOCKOUTS PROVIDED ON
5 SURFACES

285.7

[11.25]

215.9
[8.50]

216.58

[8.50]

197.47

[7.75]

41.1

[1.62]

88.9

[3.50]

190.5
[7.50]

MAX. WIRE SIZE: NO. 14 AWG
MAX. WIRE SIZE: NO. 18 AWG

SURFACE MOUNT
(FOR HANGING)

WIRES MUST BE
TWISTED (14–18 AWG)

CONDUIT AND WIRING SUPPLIED BY CUSTOMER.
MAX. DISTANCE BETWEEN SCM AND UPS NOT TO
EXCEED 500 FT.

19.0

[0.75]

FLUSH MOUNT

Figure A-29. SCM Dimensions and Mounting Details

Advertising