INSTALLING A REMOTE EMERGENCY POWER-OFF CONTROL

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201691 Rev 1 www.powerware.com

5-2

NOTE REPO switch rating is 24 Vdc, 1A minimum if supplied by the customer. The REPO switch must be a
latching-type switch with a dedicated circuit.

REPO

Switch

Twisted

Wires (2)

9

10

CUSTTB

Figure 5-2. REPO Wiring

5.

If you are installing multiple REPO stations, wire additional stations in parallel
with the first REPO.

6.

If required, install ½” conduit and wiring from the REPO station to trip circuitry of
upstream protective devices. A normally open contact is provided, as shown in
Figure 5-2. REPO switch wiring must be according to UL Class I requirements.

7.

Secure the UPS by reversing all steps taken to prepare it for REPO installation.