Heat & Glo • EXCLAIM-36C Woodburning Fireplace • 4013-093 Rev G • 08/06

11

C. Sidewalls/Surrounds

Adjacent combustible side walls must be located a minimum of 12 in. (305 mm) from the

¿ replace opening. See Figure 3.3.

If you are using a decorative surround constructed of combustible material, it must be located within the shaded area de-
¿ ned in Figure 3.3. Short stub walls are also acceptable if they are contained within the shaded area.

D. Frame the Fireplace

Figure 3.4 shows a typical framing (using 2 x 4 lumber) of the

¿ replace, assuming combustible materials are used. All re-

quired clearances to combustibles around the

¿ replace must be adhered to. See Figure 3.2. Any framing across the top of

the

¿ replace must be above the level of the top standoffs.

23-3/4 in.

(603 mm)

50°

12 in.

(305 mm)

36 in.

(914 mm)

(opening)

45-1/2 in.

(1156 mm)

(framing)

39°

4 in.

(102 mm)

BRICK

FRONT

FLUSH FRONT

12 in.

(305 mm)

19-3/4 in.

(502 mm)

Figure 3.3

Sidewalls and Surrounds

Note: Fireplace header
cannot be positioned
until the fireplace
assembly is in place.

28 in.

(711 mm)

49-3/4 in.

(1264 mm)

45-1/2 in.

(1156 mm)

49-3/4 in. (1264 mm)
header height. Use
only noncombustible
material below the top
of the front standoffs.

2 in. (51 mm)
minimum air
space clearance
to the enclosure.

Figure 3.4

Framing the Fireplace

Note: The frame of the
AED door overlaps the
f r ont of t he f ireplac e
beyond the opening by
3/4 in. (19 mm) on each
side and 1-1/2 in. (38 mm)
above the top. This should
be allowed for when apply-
ing facing to the front of the
¿ replace.

¨