Heat & Glo • EXCLAIM-36C Woodburning Fireplace • 4013-093 Rev G • 08/06

21

Slanted Roofs

Flat Roofs

Chimney must
extend 3 ft (.9 m)
above the roof

Chimney must extend 2 ft (.6 m)
above any portion of the roof
within 10 ft (3 m) of the chimney

Chimney must
extend 3 ft (.9 m)
above the roof

Chimney must extend 2 ft (.6 m)
above any portion of the roof
within 10 ft (3 m) of the chimney

Figure 6.1

Termination Requirements

Figure 6.3

Ceiling/Attic Construction

Fire Risk

Must maintain 2 in. (51 mm) air clearance
to insulation and other combustible
materials.

WARNING

Gas

Termination

Wood & Fuel Oil Termination

A

6 in.

(152 mm)

20 in.

(508 mm)

Gas, Wood or Fuel

Oil Termination

20 in.

(508 mm)

(minimum) to

Perpendicular

Wall

(gas only)

18 in.

(457 mm)

A

Gas

Termination

Figure 6.2

Multiple Chimneys

6

6

Complete the Enclosure

A. Chimney Termination

Chimney Termination Requirements (See Figures 6.1 and 6.2)

• Must have a cap approved and listed for this

¿ replace system

• Must not be located where it will become plugged by snow or other material
• Must terminate at least 3 ft (914 mm) above the roof and at least 2 ft (610 mm) above any portion of the roof within 10 ft

(3.05 m)

• Must be located away from trees or other structures

Mark the Exit Point of the Roof

Locate the point where the chimney will exit the roof by plumbing down to the
center of the chimney. Drive a nail up through the roof to mark the center. See
Figure 6.3.

Cut Out the Hole in the Roof

Measure to either side of the nail and mark the 14-1/2 in. x 14-1/2 in.
(368 mm x 368 mm) opening required. This is measured on the horizontal;
actual length may be larger depending on the pitch of the roof. Cut out and
frame the opening. See Chapter 25 of the Uniform Building Code for roof
framing details.

Assemble the Chimney Sections Through the Roof

Continue to add chimney sections through the roof opening, maintaining at
least a 2 in. (51 mm) air space to combustible materials.

Install the Roof Flashing

If a roof

À ashing is to be used, install the roof À ashing appropriate to the

roof pitch and install a round termination cap and storm collar following the
instructions shipped with the cap.