Heat & Glo • EXCLAIM-36C Woodburning Fireplace • 4013-093 Rev G • 08/06

20

E. Install the Attic Insulation Shield

An insulation shield must be installed when there is a pos-
sibility of insulation coming into contact with the factory built
chimney system.

Bend the tabs at the top of the attic insulation shield inward.
This will help keep the chimney section centered in the
shield.

Position the shield over the vertical chimney section where
it penetrates a ceiling

¿ restop.

• Slide the shield down until it rests on the ceiling

¿ restop.

The ceiling

¿ restop will support the insulation shield. See

Figures 5.6 and 5.7.

F. Double-check the Chimney Assembly

Continue assembling the chimney sections up through the
ceiling

¿ restops as needed. While doing so, be aware of the

height and unsupported chimney length limitations given un-
der Section 5.A. Chimney Requirements.

Check each section by pulling up slightly from the top to en-
sure proper engagement before installing the succeeding
sections. If they have been connected correctly, they will not
disengage when tested.

G. Secure the Chimney

When offsets and returns are joined to straight pipe sections,
they must be locked into position with the screws provided*
(outer only), using the predrilled holes. To prevent gravity
from pulling the chimney sections apart, the returns and the
chimney stabilizers have hanger straps for securing these
parts to joists or rafters. See Figure 5.8.

* or equivalent #6 or #8 sheet metal screw no longer than

3/4 in. (19 mm).

24 in.

(610 mm)

Attic

Insulation

Shield

Chimney

Insulation

13 in.

(330 mm)

17 in.

(423 mm)

Ceiling Firestop

Tabs

Figure 5.6

Install Attic Insulation Shield Above the Ceiling

Attic

Insulation

Shield

Chimney

Insulation

Ceiling Firestop

Tabs

24 in.

(610 mm)

13 in.

(330 mm)

17 in.

(423 mm)

Figure 5.7

Install Attic Insulation Shield Below the Ceiling

Ceiling
Firestop

Straps

Optional
Additional
Support

Joint

Band

(Optional)

Figure 5.8

Secure the Chimney

Fire Risk
• DO NOT pack insulation or other

combustibles: between ceiling

¿ restops;

between chimney and attic insulation
shield.

• ALWAYS maintain speci

¿ ed clearances

around chimney and ceiling firestop
systems.

• Install

ceiling

¿ restops as speci¿ ed.

Failure to keep insulation or other material
away from chimney pipe may cause

¿ re.

WARNING

Fire Risk
• Secure offsets with screws (not to exceed

3/4 in./19 mm in length).

WARNING

• Secure returns with strapping.

Straight chimney sections may be secured with screws
(not to exceed 3/4 in./19 mm in length) at the joints.

Keep chimney sections from separating or twisting.