A. Chimney Requirements

Vertical distances are measured from the base of the

¿ re-

place as shown in Figure 5.2.

To determine the chimney components needed to complete
your particular installation, follow the steps below:

• Determine the total vertical height of the fireplace

installation. This dimension is measured from the base of
the

¿ replace assembly to the point where the smoke exits

the termination cap.

Subtract the effective height of the

¿ replace assembly from

the overall height of the

¿ replace installation (measured

from the base of the fireplace to the bottom of the
termination cap).

• Refer to Table 5.1 to determine what components must

be selected to complete the

¿ replace installation.

• Determine the number of ceiling

¿ restops, stabilizers,

roof flashing, etc. required to complete the fireplace
installation.

6 ft (1.8 m) max.
unsupported run

20 ft (6 m) max.
pipe between an
offset & return

Ceiling Firestop

35 ft (10.7 m)

max. straight

unsupported

chimney height

18.5 ft (5.6 m) min. height/single offset-return

24 ft. (7.3 m) min. height/double offset-return

90 ft (27.4 m) max. height

6 ft (1.8 m) max.
unsupported chimney
above roof

71-3/4 in.

(1822 mm)

Effective Height

(bottom of fireplace

to top of starter collar)

Figure 5.2

Chimney Requirements

Table 5.1

• Do NOT connect this fireplace to a chimney flue

servicing another appliance.

• Do NOT connect to any air distribution duct or

system.

CAUTION

Fire Risk

Must maintain 2 in. (51 mm) air clearance
to insulation and other combustible
materials.

WARNING

ft

m

Minimum overall straight height

18

5.49

Minimum height with offset/return

18.5

5.64

Maximum height

90

27.43

Maximum chimney length between an
offset and return

20

6.10

Maximum distance between chimney
stabilizers`

35

10.67

Double offset/return minimum height

24

7.32

Maximum unsupported chimney length
between the offset and return

6

1.83

Maximum unsupported chimney height
above the

¿ replace

35

10.67

Maximum unsupported chimney above
roof

6

1.83

Note: A maximum of two pairs of offsets and returns may
be used.

HEIGHT OF CHIMNEY COMPONENTS

in.

mm

Chimney Stabilizer

SL4

4-3/4

121

Ceiling Firestops

FS538

0

0

FS540

0

0

Offsets/Returns

SL430

14-1/2

368

Roof Flashing

RF570

0

0

RF571

0

0

Chimney Sections*

SL406

4-3/4

121

SL412

10-3/4

273

SL418

16-3/4

425

SL436

34-3/4

883

SL448

46-3/4

1187

* Dimensions re

À ect effective height.