Heat & Glo • EXCLAIM-36C Woodburning Fireplace • 4013-093 Rev G • 08/06

34

Diagnostic Questions

Possible Causes of Condition

Solutions

Do you have glass doors?

• Need to slow air intake

Add glass doors.

What is the condition of the
wood?

• Extremely dry wood

Mix in less seasoned wood after

¿ re established.

Diagnostic Questions

Possible Causes of Condition

Solutions

Does the

¿ re start and burn

well?

No:

• Damper not fully open

Open damper; check and clean chimney if needed; use adequate
kindling and fuel; open glass doors or open window, check for
need for balanced air make-up.

• Chimney obstruction

• Not enough kindling and/or fuel to establish

draft

• Inadequate combustion air

Yes:

• Fire too close to front

Build

¿ re farther back. Do not use exhaust fans during startup

and/or check for need for balanced air make-up system.

• Competition with exhaust devices

Diagnostic Questions

Possible Causes of Condition

Solutions

Is the damper closed?

• No: Downdraft or negative pressure

Close the damper at end of burn.

• Yes: Negative pressure from exhaust fans

and/or house stack effect.

Check for need for glass doors. Check for need for balanced air
make-up system or raising chimney.

Is the chimney clean?

• No: Creosote odor

Have chimney cleaned.

• Yes: Damper closed too early

Wait until

¿ re completely out before closing damper.

I smell smoke in the house during operation. What’s causing that?

I smell smoke in the house after we’ve had a

¿ re in the ¿ replace. What is the cause/what can we do?

The

¿ replace burns the wood too fast. What can I do?