2nd heater installation, Installation (standard units), Installation (hi-lo units) – GSI Outdoors PNEG-377 User Manual

Page 75

Advertising
background image

75

Fan and Heater

2ND HEATER INSTALLATION

For Units using HF-7062 Control Board

2nd Heater Control is Available with the HF-7062 heater control board. For Standard units (1) TD-

100282 Relay must be installed. For HI-LO units (2) TD-100282 Relay must be installed. INSTAL-

LATION SHOULD BE MADE BY A QUALIFIED ELECTRICIAN. When points are called out in

instructions they are in reference to points on drawing below text.

Installation (Standard Units)

1.

Plug TD-100282 Relay into left 1 pole relay

socket on HF-7062 Control Board (This is

the socket closest to the 2PDT relay on

board See Drawing point I

2.

Run (2) wires from main heater (heater that

TD-1000282 Relay was installed in) to 2nd

heater.

3.

Connect wires to terminals 3 and 4 (Points

A and B) of 2nd heater control terminal strip

in Main heater.

4.

Connect wires to terminals 4 and 5 (points E

and F) on lower left hand corner of HF-7062

board in 2nd heater or install 2 prong plug

on wires and plug into front of control box

in receptacle marked CYCLE.

Installation (HI-LO Units)

1.

Plug (2) TD-100282 Relay into empty

sockets on HF-7062 Control board in Main

Heater.

2.

Run (4) wires from Main Heater (Heater

that TD-100282 Relay were installed in) to

2nd Heater.

3.

Connect 2 of the wires to terminals 1 and 2

(Points C and D) of 2nd Heater control

terminal strip in main heater.

4.

Connect other end of these wires to termi-

nals 2 and 3 (Points G and H) on lower left

hand corner of HF-7062 board in 2nd

heater or install 2 prong plug on wires and

plug into front of control box in receptacle

marked CYCLE.

5.

Connect other 2 wires to terminals 3 and 4

(Points A and B) of 2nd heater control

terminal strip in Main heater.

6.

Connect other end of these wires to termi-

nals 4 and 5 (Points F and G) on lower left

hand corner of HF-7062 board in 2nd

heater or install 2 prong plug on wires and

plug into front of control box in receptacle

marked HI-LIMIT.