Fenwal-series 05-14 – GSI Outdoors PNEG-377 User Manual

Page 92

Advertising
background image

92

Fan and Heater

Control Board

Comments

Gas Valve Relay

Current Ratings:

A) 05-14X201-00X Common relay output

05-14X401-00X 120VAC 1 amp

B) 05-14X301-00X Isolated valve contacts

05-14X501-00X 1) 24VAC 2amps

2) 120VAC 1amps

3) 240VAC 0.5amps

Timing

(Trial -for-Ignition)

-000: 3.3 seconds

-001: 4.7 seconds

-005: 10 seconds

Electrodes

05-100000-XXX*: Gap 0.125" = 0.031"

or

22-100000-XXX*:

*Last three digits designate configuration

Lead Wire

05-125978-0XX**: High Voltage

05-125979-0XX**: Low Voltage

CAUTION: If ambient temperature ratings are

exceeded, damage to the unit and/or improper

operation may result.

** Last Two digits designate length of wire in

inches. EX: -024 = 24 inches. When ordering,
specify length required.

Wiring

IMPORTANT: The model number of each

Fenwal Spark Ignition Module is stamped on a lable

attached to the high voltage transformer. Select the

electrical ciruit diagram in Figure 3 which matches

the model number on the high voltage transformer

and wire the unit accordingly.

NOTE: The burner and the 120V suppy (NEUT-

L2) must be grounded to obtain satisfactory opera-

tion. Failure to do so will prevent ignition from

lasting beyond the trial for ignition period.

Fenwal Gas Ignitors are provded with 1/4" male

quick connect terminals (ARK-LES Part No. 300

H19A or recommended equivalent should be used

for all connections.) When making connections, be

Warning: Do not apply power to imput terminals

unless electrode is properly connected and

grounded or damage to the unit may result.

System Checks

Preliminary System Checks

It is desireable to checks the system after installa-

tion and before gas supply is turned on.

Be sure that the input is polarized as shown on

wiring diagrams and the installation is electrically

grounded. Cabinet, electrode and burner must

have a common ground. Connect as shown in

proper diagram in Figure 3, page 73.

Polarity Check

1.

With voltmeter or indicator light,

measure from Terminal A (L1) to ground.

Voltage should be 120V.

2.

Measured from L2 to ground. Voltage

should be "0".

3.

If 1 and 2 above are opposite, reverse

input leads to insure correct polarity.

Initial Operation

1.

Check installation, mounting and elec

trode gap to insure conformance to

specifications.

V

sure they conform to both U.L. and local codes.

NOTE:High voltage lead wire should be routed at

least 1 inch from metal piping or metal frames.

Do not wrap or bundle any wires with or against

the high-voltage lead wire.

CAUTION: HIGH VOLTAGE

NOTE: Although epoxy coated to insure proper

operation at 90% relative humidity, good electrical

practice should be followed. Insure the control is

mounted so that total water immersion will not

result. If such a condition occurs, unit should be

cycled to the OFF position and inspected by a

qualified service person before recycling.

FENWAL-SERIES 05-14

continued on page 74