Fan and Heater

FENWAL-SERIES 05-14

Operation continued

This manual reset button can be located on the

ignitor board or remotely on a control panel.

(Consult factory for remove mounting agency

approvals). Should the flame not be established

during the trial for ignition period, the system will

lock-out. Should flame-out occur any time during

the duty cycle, the system will retry for ignition,

one time, and then lock-out. The manual reset

button will then trip within several seconds. After 5

second, depress the reset button to reset the control

module.

Flame Sensing

The Series 05-14 ignitor is designed to operate with

a single electrode assembly, which provides the

spark and senses the presence of flame. See Figure

3 Aor B. Remote sensing models, however, allow

for the flame sensing function to be separated from

the spark function and located remotely. See Figure

3C or D. Utilization of remote sensing insures

flame propagation across and entire burner pack.

Electrode Application

(Burner Manufacturer only)

1.

Manually ignite burner flame to observe

flame characteristics.

2.

Temporarily mount electrode directly over

burner parts in blue part of flame pattern.

Electrode tips should be 1/4 to 1/2-inch

above parts. Mount electrodes so that both

tips are immersed approximately 1/2-inch

into the flame with 1/8-inch spark gap

directly over a port. See Figure 1.

Figure 1

3.

Connect the electrode lead wires to the

control module. See Figure 3. Make

certain that the remaining system wiring is

complete.

4.

With the gas supply m;anually shut off,

cycle the thermostat to operate the control

module. Insure that steady sparking occurs

at electrode tips. Sparking should not

occur elsewhere.

5.

Cycle thermostat to OFF position or

depress reset button and manually restore

gas supply.

6.

Cycle thermostat on ON position noting

that sparking occurs immediately and that

the flame is established within a period of

no more than four seconds. Once the

flame is established, sparking will cease.

7.

If ignition is achieved within four seconds

and sparking terminates immediately after

flame is established, you have a

functionaaly sound installation. However,

should these requisites not be met, consult

the "System Checks" section on page 4 for

remedial recommendations.

NOTE: Electrode assemblies are presision components and

should not be adjusted or disassembled. Electrodes should

have a gap spacing of 0.125"=0.031". If this spacing is not

correct, return the electrode assembly to the factory for

replacement. Electrodes are NOT field adjustable.

Specifications

Control Board

Comments

05-14X201-00X: 120VAC valve relay, local sensing

05-14X301-00X: Isolated valve contacts, local

sensing

05-14X401-00X: 120VAC valve relay, remote

sensing

05-14X501-00X: Isolated valve contacts, remote

sensing

X (Fifth Digit) 0=Manual Reset

2=Thermostat Reset

Input Voltage: 120VAC, 60Hz, nominal

Current Drain: 50mA (175mA to 250mA momen-

tarily during ignition).

Ambient: -40°F to 140°F, operating