FLAME DETECTOR KIT INSTALLATION

1991-1993

Flame Detector Kit Installation

Part Number HF-7136

1.

Mount the detector module inside the

heater control box. Module can be

mounted in any position, but install so

that moisture cannot get inside unit.

2.

Run white wire to common or neutral

of 120V power source.

3.

Run black wire to terminal that is 110V

when heater gets power. (Wire module

power in parallel with ignition trans

former or main solenoid if they are

110V.)

4.

Run green and red wires down to sens-

ing probe. Red wire should go to flame

probe electrode and green wire should

go to flame probe ground. For proper

operation the ground wire should be

connected as close to probe as possible.

5.

The remaining three wires are the

normally open or normally closed relay

contacts that replace the mechanical

flame probe. The blue-black wire is the

common, the white-brown wire is the

normally closed, and the white-blue is

the normally open. On all Airstream

heaters use the blue-black and the

white-brown wires. The white-blue

wire should be used only on makes of

heaters that use a normally open probe.

6.

Mount the sensing probe so the sensing

portion will be in the flame at its highest

and lowest operating conditions.

7.

Inside the flame detector is a red neon

light. This light should be on when

flame is being sensed and will go out

when flame out condition is detected.

NOTE: IF PROBE DOES NOT SEEM TO SENSE FLAME AS IT SHOULD REVERSE THE

RED AND GREEN WIRES AT THE PROBE. THIS MAY INCREASE SENSITIVITY OF

PROBE ON CERTAIN MAKES OF HEATERS.

FLAME

DETECTOR

MODULE

CONNECT WHERE

MECHANICAL PROBE

WIRES WERE CONNECTED

NORMALLY OPEN WHITE/BLUE

COMMON BLUE/BLACK

NORMALLY CLOSED WHITE/BROWN

V

TO FLAME SENSOR ELECTRODE RED

GROUND GREEN

V

TO FLAME SENSOR

BLACK

WHITE

V