Self-operated modulating valves, Installation and operation instructions – GSI Outdoors PNEG-377 User Manual

Page 87

Advertising
background image

87

Fan and Heater

SELF-OPERATED MODULATING VALVES

Series V50

Self-Operated Modulating Valves

For Outdoor Crop Dryer Service

Johnson Controls, Inc.

Control Products Division

1302 East Monroe Street

Goshen, IN 46526

Installation and Operation

Instructions

Application

These valves control the flow of gas on natural or LP

gas fired outdoor crop dryers to maintain desired

drying air temperature. Changes in air temperature at

the sensing bulb cause the valve to modulate the gas

supply to the main burner.

CAUTION: Valves are for outdoor crop dryer

service only. Not for use on applications of any other

kind.

All Series V50 valves are designed for use only as

operating devices. Where system closure, improper

flow or loss of pressure due to valve failure can result

in personal injury and/or loss of property, a separate

pressure relief or safety shutoff valve, as applicable,

must be added by the user.

Operation

LP Gas Application

These valves are normally located on the crop dryer

gas manifold between the pressure regulating valve

and the burner orifice. They are used on vapor

withdrawal systems or on liquid withdrawal systems

using a direct or indirect vaporizer. They should not

be used as a expansion valves (handling liquid LP) on

straight liquid withdrawal systems.

A pressure regulating valve is required to maintain

uniform inlet pressure to the V50 modulating valve

because the tank pressure varies considerably due to

changes in tank ambient temperature.

The recommended setting for the pressure regulating

valve is no higher than 30PSIG (207 kPa) as in many

instances the outside temperature will not be high

enough to provide the regulating valve with

pressure above this value. The maximum working

pressure for V50 self-operating valves is 30 PSIG.

As the modulating valve provides only a portion of

the pressure drop, the maximum firing rate (valve

wide open) is determined by the setting of the

pressure regulator and the size of the burner

orifice.

Installation

Follow original equipment manufacturer's installa-

tion instructions, if provided.

CAUTION: The valve should not be installed on

lines where line pressure excedds 30 PSIG (207

kPa). When there is a possibility of pressures over

30 PSIG, provide an overpressure or alarm

control. The temperature at the sensing bulb must

not exceed maximum valve range shown on the

nameplate by more than 20F° (10C°). The maxi-

mum ambient temperature around the valve body

must nots exceed 175°F (79°C).

Figure 1

Modulating Value V50A

Figure 2

Modulating Value V50B