FX2N-32DP-IF Profibus-DP Interface Unit

Introduction 1

1-8

1.3.3

Configuration Rules

1) Special function blocks: Max. 8 blocks per 32DP-IF.

Check the loading on the 5 V DC bus supply. Consumption values for special function
blocks can be found in Table 1.7. For maximum available current see the Table 1.6.

2) Maximum I/O points: 256 or less.

3) Check the loading on the 24 V DC service supply. Look up the number of expansion I/O in

Figure 1.4. Find the residual current. This can then be used to power sensors etc.

4) Check total exchanged data length in DP-master, this number might be limited by the DP-

master unit. Data length is exchanged between the 32DP-IF and a DP-master in every
cycle.
For the data length of connected extension units/blocks, refer to Table 1.3.
However, the maximum amount of data that can be exchanged with the 32DP-IF is 200 byte
inputs and 200 byte outputs.

Figure 1.4: Number of Expansion I/O and 24 V DC Service Supply Capacity (mA)

For extension unit, refer to FX

2N

Series Hardware Manual.

Table 1.6: 24 and 5 V DC Supply Capacity

Items

Power Supply

24 V DC Service Supply

500 mA at 24 V DC

Max. 5 V DC Bus Supply

220 mA at 5 V DC

Table 1.7: Power Supply for Special Function Blocks

Model

Description

Number of

I/O Points

Power Supply

Internal 5 V DC

(mA)

External 24 V DC

(mA)

FX

2N

-4DA

Digital to analog converter

8

30

200

FX

2N

-4AD

Analog to digital converter

8

30

55

FX

2N

-4AD-PT

PT100 probe interface

8

30

50

FX

2N

-4AD-TC

Thermo-couple interface

8

30

50

Number of
additional
output
(points)

> 32

32

200

150

100

50

0

Invalid configuration

24

275

225

175

125

75

25

16

350

300

250

200

150

100

50

0

8

425

375

325

275

225

175

125

75

25

0

500

450

400

350

300

250

200

150

100

0

8

16

24

32

40

48

56

64

> 64

Number of additional input (points)

Advertising