2 configuring slave parameter, 1 configuring slave parameter by gsd file, 2 configuring slave parameter by programming tool – MITSUBISHI ELECTRIC FX2N User Manual

Page 44: Configuring slave parameter -4

Advertising
background image

FX2N-32DP-IF Profibus-DP Interface Unit

User Parameter 6

6-4

6.2

Configuring Slave Parameter

Caution:

The user parameter data and configuration of the 32DP-IF must always be consistent. To
ensure that the user parameter data and the configuration of the 32DP-IF are matching
each other, the user parameter data set should always be constructed by using the GSD file
that has been delivered with the 32DP-IF.

6.2.1

Configuring Slave Parameter by GSD file

The parameter setting of the 32DP-IF can be entirely defined using the GSD file that comes on
the disk together with 32DP-IF. For an easy adjustment of all user parameter data, the
Mitsubishi Profimap Software V2.X or a configuration software from another vendor which is
supporting extended parameter setting should be used.

Note:

In configuring 32DP-IF GSD file, first assign special function blocks, second extension I/O
units/blocks’ input data, and finally extension I/O units/blocks’ output data. The physical
placement of the module does not have to correspond with the GSD file order.

6.2.2

Configuring Slave Parameter by Programming Tool

The process of defining a parameter using the programming tool is shown in Figure 6.3.

Please only use a programming tool if configuring a single special function block. It is recom-
mended to utilize the functionality of the GSD file when configuring more than one. As it is
much easier to use for this purpose.

Caution:

Any mistake in changing D200 ~ D299 can lead to a different interptetation of the Profibus-
DP data, which can result in a malfunction of the connected I/O units/blocks and special
function blocks.

Figure 6.3: Process Making Parameter Data by Programming Tool

1. Input parameter data in D200 ~ D299.

2. Turning M8020 from OFF to ON, 32DP-IF send parameter
(D200 ~ D299) extention units/blocks. After this data
furnish to be sent, M8020 is reset automatically.

3. Setting end

Advertising