2 error flags, 2 error flags -4 – MITSUBISHI ELECTRIC FX2N User Manual

Page 50

Advertising
background image

FX2N-32DP-IF Profibus-DP Interface Unit

Diagnostics 8

8-4

8.3.2

Error Flags

Table 8.6: Error Flags

Diagnostic

Device

Name

Check Points

M8004
(ref. D8004)

Error occurrence

ON when one or more error flags (M8060 to
M8068) is ON. If this bit is ON, error number is
written in D8004.

M8060
(ref. D8060,
D8061)

I/O configuration error

If this flag is ON, check error code in D8060,
D8061 and extension cable.

M8061
(ref. D8060,
D8061)

32DP-IF hardware error

If this bit is ON, check error code in D8061.

M8062
(ref. D8062)

PC/HPP communication error

If this bit is ON, check error code in D8062.

M8064
(ref. D8064

Parameter error

If this flag is ON, check error code inD8064 and
DP-master setting.

M8067
(ref. D8067)

Operation error

If this flag is ON, check error code in D8067 and
D8068, DP-master parameter, and the extension
cable.

M8068
(ref. D8068)

Parameter error and operation
error

If M8064 or M8067 is ON, this bit would be set to
ON. This bit is cleared by resetting the power
supply.