FX2N-32DP-IF Profibus-DP Interface Units

Appendix B

B-8

2) Second step in adjusting offset/gain

a) Second step in adjusting offset/gain for FX

2N

-4AD

Table B-8: Second Step in Adjusting Offset/Gain for FX

2N

-4AD

Using GSD File

User

Parameter

Type

Description

Using Programming Tool

Byte

No.

Setting

Value

(Hex)

Register

No.

Setting

Value

(Hex)

Higher/

Lower

Byte

0

00 H

User
parameter
for 32DP-IF

See section 6.1.

D200

0000 H

Lower

1

00 H

Higher

2

DA H

User
parameter
for special
function
block
(FX

2N

-4AD)

BFM #30 lower byte “DA H”

D201

07DA H

Lower

3

07 H

BFM #30 higher byte “07 H”

Higher

4

0F H

Total length of parameter bytes for this
special function block is 15 bytes (byte
No. 4 ~ 18).

D202

040F H

Lower

5

04 H

Example: number of BFM for data

exchanged every cycle is 4
BFMs (BFM #9 ~ #12).

Higher

6

09 H

Specified exchange, ex. BFM #9

D203

0A09 H

Lower

7

0A H

Specified exchange, ex. BFM #10

Higher

8

0B H

Specified exchange, ex. BFM #11

D204

0C0B H

Lower

9

0C H

Specified exchange, ex. BFM #12

Higher

10

97 H

Example: If offset data is set to “0 V”,

BFM #23 is set to “0000 H”.

D205

H0097

Lower

11

00 H

BFM #23 lower byte: “00 H”

Higher

12

00 H

BFM #23 higher byte: “00 H”

D206

9800 H

Lower

13

98 H

Example: If gain data is set to “7 V”,

BFM #24 is set to “1B58 H”

Higher

14

58 H

BFM #23 lower byte: “58 H”

D207

1B58 H

Lower

15

1B H

BFM #23 higher byte: “1B H”

Higher

16

96 H

Example: If adjusting ch 1, BFM #22 is

set to “0003 H”

D208

0396 H

Lower

17

03 H

BFM #22 lower byte: “03 H”

Higher

18

00 H

BFM #22 higher byte: “00 H”

D209

0000 H

Lower

-

-

-

Higher