B-1-2 example setting for fx2n-4da, B-1-2 example setting for fx – MITSUBISHI ELECTRIC FX2N User Manual

Page 56

Advertising
background image

FX2N-32DP-IF Profibus-DP Interface Units

Appendix B

B-2

B-1-2

Example Setting for FX

2N

-4DA

For BFM’s definition, refer to FX

2N

-4DA User’s Manual.

Table B-2: User Parameter For FX

2N

-4DA

Using GSD File

User

Parameter

Type

Description

Using Programming Tool

Byte No.

Setting

Value

(Hex)

Register

No.

Setting

Value

(Hex)

Higher/

Lower

Byte

0

00 H

User
parameter
for 32DP-IF

See section 6.1.

D200

0000 H

Lower

1

00 H

Higher

2

CC H

User
parameter
for special
function
block
(FX

2N

-4DA)

BFM #30 lower byte: “CC H”

D201

0BCC H

Lower

3

0B H

BFM #30 higher byte: “0B H”

Higher

4

09 H

Total length of parameter bytes for this
special function block is 9 bytes (byte
No. 4 ~ 12).

D202

0409 H

Lower

5

04 H

Example: number of BFM for data

exchanged every cycle is 4
BFMs (BFM #1 ~ #4).

Higher

6

01 H

Specified exchange, ex. BFM #1

D203

0201 H

Lower

7

02 H

Specified exchange, ex. BFM #2

Higher

8

03 H

Specified exchange, ex. BFM #3

D204

0403 H

Lower

9

04 H

Specified exchange, ex. BFM #4

Higher

10

80 H

Example: If BFM #0 is set to “0000 H”.

Ch 1: Voltage output mode
Ch 2: Voltage output mode
Ch 3: Voltage output mode
Ch 4: Voltage output mode

D205

0080 H

Lower

11

00 H

BFM #0 lower byte = “00 H” (ch 1, ch 2)

Higher

12

00 H

BFM #0 higher byte = “00 H” (ch 3, ch 4)

D206

0000 H

Lower

-

-

-

Higher

Advertising