Diagnostic message, 1 diagnostic massage frame, 2 diagnostic message contents list – MITSUBISHI ELECTRIC FX2N User Manual

Page 45: Diagnostic message -1, Diagnostic massage frame -1, Diagnostic message contents list -1

Advertising
background image

Diagnostic Message 7

7-1

7.

Diagnostic Message

7.1

Diagnostic Massage Frame

When a diagnostic error occurs in the 32DP-IF, a diagnostic message is sent form the 32DP-IF
to the DP-master as shown in Figure 7.1. Refer to section 4.2 for the diagnostic message
description.

Note:

If the DP-master receives a diagnostic message, make provisions for the system to act
safely in accordance with the error message.

Figure 7.1: Diagnostic Massage Frame

*1 This diagnostic message is either number of momentary power failures or the error code

relating to the contents of D8004 (byte No. 3, 4). For error code, refer to section 4.2.4 or
8.3.3.

*2 This diagnostic message is either “0” or the contents of D8068.

7.2

Diagnostic Message Contents List

Byte No.

0

1

2

3

Description

Total length of diag-
nostic massage data
is 9 (09 Hex)

First diagnostic message

Second diagnostic

message

Lower byte of D8029

Higher byte of D8029 Lower byte of D8004

Byte No.

4

5

6

7

Description

Second diagnostic

message

Third diagnostic message

Lower byte of last
diagnostic message

data

*2

Higher byte of D8004

Lower byte of diag-

nostic

*1

Higher byte of error

code

*1

Byte No.

8

Description

Higher byte of last
diagnostic message

data

*2

Table 7.1: Diagnostic Message List

Item

Third diagnostic message

Last diagnostic message

32DP-IF status is STOP

This velure is “0”.

This velure is “0”.

Momentary power failure

This velure is number of momentary
power failures in D8007.

Power down

I/O bus error

This velure is error code in D8061.

This velure is in D8068.

Parameter error

This velure is error code in D8064.

Operation error

This velure is error code in D8067.

FX2N-32DP-IF Profibus-DP Interface Unit

Advertising