FX2N-32DP-IF Profibus-DP Interface Unit

Advanced Devices 4

4-5

4.2.2

Profibus-DP Network Status (M8020 ~ M8039 and D8020 ~ D8039)

Note 1: Swap byte order

Some DP-masters handle lower bytes and higher bytes of a word in a reverse order than the 32DP-
IF. To enable the module to communicate with these masters, bit 0 of data register D8021 can be set.
If bit 0 is “1”, the low order byte and the high order byte of each user data word and of the user spe-
cific diagnosis will be swapped. Bit 0 of D8021 can also be set or reset by the second user defined
parameter byte received from a master. The default value after power up is “0”.

Table 4.5: Special Auxiliary Relays (M8020 ~ M8039)

Diagnostic

Device

Name

Description

M8020

Setting parameter

When this bit is changed from OFF to ON, the parameter D200
~ D299 (made by the programming tool) is written to special
function blocks’ BFM. After the write is completed, this bit is
turned automatically to OFF.

M8021 ~ M8033

Reserved

M8034

All output disable

All physical switch gear for activating outputs is disabled. How-
ever, for debugging purposes the logical state of these outputs
(D100 ~ D199) can be set, but remain disabled in the actual
module.

M8035 ~ M8039

Reserved

Table 4.6: Special Data Registers (D8020 ~ D8039)

Diagnostic

Device

Name

Description

D8020

(



)

Data exchange
status

Data register D8020 contains a status bit for data exchange.
If this is “1”, 32DP-IF is in data exchange mode.
If this is “0”, 32DP-IF is not in data exchange mode.

D8021

(



)

Swap byte order

See note 1.

D8022

(



)

Length of input
(sent) data in byte

The values held in these devices are copied from the input data
length and output data length setting in the DP-master.

D8023

(



)

Length of output
(received) data in
byte

D8024

(



)

Baud rate

See note 2.

D8025

(



)

Communication
status

See note 3.

D8026

(



)

Profibus module
ID (PNO ID code)

PNO-Nr.F232 (Hex)
(This number contains the Profibus module ID number for the
32DP-IF.)

D8027

(



)

Slave address

The slave address is set only by the 32DP-IF’s DIP switches.
The slave address value is 0 to 126. The address change by a
Profibus-DP Class 2 master via the network or by a program-
ming device is not supported.

D8028

Reserved

D8029

(



) (



)

Error status

See note 4.