B-1-4 example setting for fx2n-4ad-tc, B-1-4 example setting for fx – MITSUBISHI ELECTRIC FX2N User Manual

Page 58

Advertising
background image

FX2N-32DP-IF Profibus-DP Interface Units

Appendix B

B-4

B-1-4

Example Setting for FX

2N

-4AD-TC

For BFM’s definition, refer to FX

2N

-4AD-TC User’s Manual.

Table B-4: User Parameter for FX

2N

-4AD-TC

Using GSD File

User

Parameter

Type

Description

Using Programming Tool

Byte No.

Setting

Value

(Hex)

Register

No.

Setting

Value

(Hex)

Higher/

Lower

Byte

0

00 H

User
parameter
for 32DP-IF

See section 6.1.

D200

0000 H

Lower

1

00 H

Higher

2

EE H

User
parameter
for special
function
block
(FX

2N

-4AD-

TC)

BFM #30 lower byte: “EE H”

D201

07EE H

Lower

3

07 H

BFM #30 higher byte: “07 H”

Higher

4

09 H

Total length of parameter bytes for this
special function block is 9 bytes (byte
No. 4 ~ 12).

D202

0409 H

Lower

5

04 H

Example: number of BFM for data

exchanged every cycle is 4
BFMs (BFM #9 ~ #12).

Higher

6

09 H

Specified exchange, ex. BFM #9

D203

0A09 H

Lower

7

0A H

Specified exchange, ex. BFM #10

Higher

8

0B H

Specified exchange, ex. BFM #11

D204

0C0B H

Lower

9

0C H

Specified exchange, ex. BFM #12

Higher

10

80 H

Example: If BFM #0 is set to “1100 H”.

Ch 1: K type
Ch 2: K type
Ch 3: J type
Ch 4: J type

D205

009C H

Lower

11

00 H

BFM #0 lower byte = “00 H” (ch 1, ch 2)

Higher

12

00 H

BFM #0 higher byte = “11 H” (ch 3, ch 4)

D206

0000 H

Lower

10

9C H

Example: If BFM #28 is set to “0000 H”,

all digital range error flags are
reset.
Bit 0 ~ bit 7 for digital range
error flags are all OFF (0)) in
the BFM #28.

D205

009C H

Lower

11

00 H

BFM #0 lower byte = “00 H”

Higher

12

00 H

BFM #0 higher byte = “00 H”

D206

0000 H

Lower

-

-

-

Higher

Advertising