FX2N-32DP-IF Profibus-DP Interface Unit

Wiring and Mounting Arrangements 2

2-3

2.2.2

Wiring for 32DP-IF and Profibus-DP Network

To connect the 32DP-IF to a Profibus-DP network use only the Profibus connectors and
shielded twisted-pair cable complying with EN50170.

Please use terminating resistors and Profibus connectors as shown in the DP-master manual
and Profibus connector manual.

The 32DP-IF does not have a terminating resistance built-in.

Figure 2.4: Wiring about 32DP-IF and Profibus-DP Network

Figure 2.5: Wiring for Power Line Circuit

Figure 2.6: Profibus Connector

100 ~ 240 V AC

L

COM

24+

FX

2N

-32DP-IF

Profibus-DP
Interface Unit

N

Power line

circuit

Service supply

For power circuit,
refer to Figure 2.5.

For Profibus
connector, refer
to Figure 2.6.

Shielded twisted-pair
cable complying with
EN50170 to Profibus-
DP network

Grounding plate

Grounding
resistance of
100

or less

(Class 3)

For noise prevention please attach at least 50 mm
(1.97") of the twisted-pair cable along the grounding
plate to which the ground terminal is connected.

MC

MC

MC

MC

Fuse

Connect to "N" terminals

Power supply
for loads

Power supply
for loads

100 ~ 240 V AC

Emergency stop

Circuit protection device

Connect to "L" terminals

Shielded twisted-pair cable to
Profibus-DP network

FX

2N

-32DP-IF Profibus

Interface-DP Unit