Specifications, 1 general specifications, 2 power supply specifications – MITSUBISHI ELECTRIC FX2N User Manual

Page 25: Specifications -1, General specifications -1, Power supply specifications -1

Advertising
background image

Specifications 3

3-1

3.

Specifications

3.1

General Specifications

3.2

Power Supply Specifications

Table 3.1: General Specifications

Item

Description

Operating Temperature

0 to 55 °C (32 to 131 °F)

Storage Temperature

-20 to 70 °C (-4 to 158 °F)

Operating Humidity

35 to 85% Relative Humidity, No condensation

Storage Humidity

35 to 90% Relative Humidity, No condensation

Vibration Resistance
- Direct Mounting

Conforms to JIS C0040; 10 - 57 Hz: 0.75 mm Half Amplitude

57 - 150 Hz: 9.8 m/s

2

Acceleration

Sweep Count for X, Y, Z: 10 times (80 min in each direction)

Vibration Resistance
- DIN rail Mounting

Conforms to JIS C0040; 10 - 57 Hz: 0.035 mm Half Amplitude

57 - 150 Hz: 4.9 m/s

2

Acceleration

Sweep Count for X, Y, Z: 10 times (80 min in each direction)

Shock Resistance

Conforms to JIS C0041: 147m/s

2

Acceleration, Action Time: 11 ms

3 times in each direction X, Y, and Z

Noise Immunity

1,000 Vp-p, 1microsecond, 30 - 100 Hz, tested by noise simulator

Dielectric Withstand Voltage 1,500 V AC > 1 min, tested between all points, terminals and ground

Insulation Resistance

5 M

> at 500 V DC, tested between all points, terminals and ground

Grounding

Class 3 (Grounding resistance is 100

or less)

Planned Certifications

CE

Table 3.2: Power Supply Specifications

Item

Description

Power Supply

100 ~ 240 V AC +10% -15%, 50/60 Hz

Max. Allowable Momentary
Power Failure Period

10 ms at 100 V AC
(< 10 ms, 32DP-IF = RUN continue, > 10 ms, 32DP-IF = power down)

Fuse (size) Rating

3 A <

φ

5

×

20 mm (0.2

×

0.79 inches)>

In-rush Current

100 V AC Max. 40 A < 5 ms, 200 V AC Max. 60 A < 5 ms

Power Consumption

35 VA

24 V DC Service Supply

500 mA

Max. 5 V DC Bus Supply

220 mA

FX2N-32DP-IF Profibus-DP Interface Unit

Advertising