3 check error status of the 32dp-if, 1 error status in d8029, Check error status of the 32dp-if -3 – MITSUBISHI ELECTRIC FX2N User Manual

Page 49: 1 error status in d8029 -3

Advertising
background image

FX2N-32DP-IF Profibus-DP Interface Unit

Diagnostics 8

8-3

8.3

Check Error Status of the 32DP-IF

8.3.1

Error Status in D8029

Table 8.5: Error Status in D8029

Bit No.

Description

0 (OFF)

1 (ON)

Bit 0

general error

No general error

This bit is ON if one or more error bits (bit 2, 6,
7) are ON. Check bit 2, 6 and 7 in D8029.

Bit 1

Reserved

Bit 2

Power fail

Power supply is
normal

Power supply failure

Bit 3 ~ 5

Reserved

Bit 6

I/O bus error

No I/O bus error

I/O bus error occurred. Check extension bus
cable of I/O extension units/blocks and error
code in D8060.

Bit 7

Operation error

No operation error

Operation error occurred. Check extension bus
cable of special function blocks, and DP-master
parameter, and error code in D8067 and
D8068.

Bit 8, 9

Reserved

Bit 10

configuration error

Configuration
data valid

Invalid configuration data received. Check con-
figuration of 32DP-IF in the DP-master and
D8040 ~ D8055.

Bit 11

Parameter error

Parameter data
valid

Invalid parameter data received. Check param-
eter of 32DP-IF in the DP-master and D200 ~
D299, and error code in D8064and D8068.

Bit 12 ~ 14 Reserved

Bit 15

RUN/STOP status

RUN/STOP
switch is in RUN
position

RUN/STOP switch is in STOP position