B-4 changing the high speed mode/normal mode – MITSUBISHI ELECTRIC FX2N User Manual

Page 65

Advertising
background image

FX2N-32DP-IF Profibus-DP Interface Units

Appendix B

B-11

B-4

Changing the High Speed Mode/Normal Mode

The user parameter settings are as shown in FX

2N

-4AD example. For FX

2N

-4DA, the settings

must correspond to their respective BFM locations. For definitions of the BFM’s, refer to each
modules user’s manual.

Table B-11:Changing the High Speed Mode/Normal Mode for FX

2N

-4AD

Using GSD File

User

Parameter

Type

Description

Using Programming Tool

Byte

No.

Setting

Value

(Hex)

Register

No.

Setting

Value

(Hex)

Higher/

Lower

Byte

0

00 H

User
parameter
for 32DP-IF

See section 6.1.

D200

0000 H

Lower

1

00 H

Higher

2

DA H

User
parameter
for special
function
block
(FX

2N

-4AD)

BFM #30 lower byte

D201

07DA H

Lower

3

07 H

BFM #30 higher byte

Higher

4

09 H

Total length of parameter bytes for this
special function block is 9 bytes (byte
No. 4 ~ 12).

D202

0409 H

Lower

5

04 H

Example: number of BFM for data

exchanged every cycle is 4
BFMs (BFM #9 ~ #12).

Higher

6

09 H

Specified exchange, ex. BFM #9

D203

0A09 H

Lower

7

0A H

Specified exchange, ex. BFM #10

Higher

8

0B H

Specified exchange, ex. BFM #11

D204

0C0B H

Lower

9

0C H

Specified exchange, ex. BFM #12

Higher

10

8F H

Example: Using high speed mode, BFM

#15 is set to “0001 H”.

D205

018F H

Lower

11

01 H

BFM #15 lower byte: “01 H”

Higher

12

00 H

BFM #15 higher byte: “00 H”

D206

0000 H

Lower

-

-

-

Higher

Advertising