FX2N-32DP-IF Profibus-DP Interface Unit

Advanced Devices 4

4-7

Note 3: Communication status

This device is the 32DP-IF’s communication status. According to the status of 32DP-IF the
bits are set and reset as follows.

*1 Clear data global control:

When this command is received, the 32DP-IF set to “0” the output
data (D100 ~ D199) of extension units/blocks connected it.

*2 Unfreeze global control:

The UNFREEZE control command stops freeze control mode. The
input data (D0 ~ D99) of extension units/blocks connected to the
32DP-IF is immediately sent to the DP-master.

*3 Freeze global control:

The DP-master sends a FREEZE control command to a group of DP-
slaves to hold their current input status. The input data (D0 ~ D99) of
extension units/blocks connected to the 32DP-IF are withheld until
the next FREEZE/UNFREEZE control command is received.

*4 Unsync global control:

The UNSYNC command stops SYNC control mode. The output data
(D100 ~ D199) send from the DP-master is immediately transmitted
to extension units/blocks connected to the 32DP-IF.

*5 Sync global control:

The DP-master sends a SYNC control command to a group of DP-
slaves to synchronize their current output states. The output data
(D100 ~ D199) of extension units/blocks connected to the 32DP-IF
remains constant until the next SYNC/UNSYNC command is
received.

Table 4.8: Communication Status in D8025

Bit No.

Description

1 (ON)

0 (OFF)

Bit 0

Module on-line/off-line

Module on-line

Module off-line

Bit 1

Reserved

BIt 2

Diagnosis flag

New diagnosis not yet fetched by
DP-master

New diagnosis fetched by
DP-master

Bit 3

Reserved

Bit 4, 5

DP-status

(bit 5, 4) = (0, 0)

Wait parameter state

(bit 5, 4) = (0, 1)

Wait configuration state

(bit 5, 4) = (1, 0)

Data exchange state

(bit 5, 4) = (1, 1)

Not possible

Bit 6, 7

DP-watchdog state

(bit 7, 6) = (0, 0)

Baud search state

(bit 7, 6) = (0, 1)

Baud control state

(bit 7, 6) = (1, 0)

DP search state

(bit 7, 6) = (1, 1)

Not possible

Bit 8

Reserved

BIt 9

Clear data global control

*1

Clear data command received

No clear data command received

Bit 10

Unfreeze global control

*2

Unfreeze command received

No unfreeze command received

Bit 11

Freeze global control

*3

Freeze command received

No freeze command received

Bit 12

Unsync global control

*4

Unsync command received

No unsync command received

Bit 13

Sync global control

*5

Sync command received

No sync command received

Bit 14, 15 Reserved