4 error status (m8060 ~ m8069 and d8060 ~ d8069) – MITSUBISHI ELECTRIC FX2N User Manual

Page 36

Advertising
background image

FX2N-32DP-IF Profibus-DP Interface Unit

Advanced Devices 4

4-10

4.2.4

Error Status (M8060 ~ M8069 and D8060 ~ D8069)

Table 4.11:Special Auxiliary Relays (M8060 ~ M8069)

Diagnostic

Device

Name

Check Points

M8060

(



) (



)

(ref. D8060,
D8061)

I/O configuration error

If this flag is ON, check error code in D8060,
D8061 and extension cable.

M8061

(



) (



)

(ref. D8060,
D8061)

32DP-IF hardware error

If this bit is ON, check error code in D8061.

M8062, M8063

Reserved

M8064

(



) (



)

(ref. D8064

Parameter error

If this flag is ON, check error code inD8064 and
DP-master setting.

M8065, M8066

Reserved

M8067

(



) (



)

(ref. D8067)

Operation error

If this flag is ON, check error code in D8067 and
D8068, DP-master parameter, and the extension
cable.

M8068

(



)

(ref. D8068)

Parameter error and operation
error

If M8064 or M8067 is ON, this bit would be set to
ON. This bit is cleared by resetting the power
supply.

M8069

Reserved