Features, Specifications, Bladecenter – IBM BladeCenter T Type 8720 User Manual

Page 15: Type, Unit

Advertising
background image

Features

and

specifications

for

the

BladeCenter

T

Type

8720

unit

The

following

table

provides

a

summary

of

the

features

and

specifications

of

the

BladeCenter

T

Type

8720

unit.

Table

1.

BladeCenter

T

Type

8720

features

and

specifications

Media

tray

(on

front):

v

DVD/CD-RW

drive:

slim

IDE

v

Two

Universal

Serial

Bus

(USB)

v2.0

full

speed

ports

v

System-status

panel

Module

bays

(on

front):

v

Eight

hot-swap

blade

bays

v

Four

hot-swap

power-module

bays

v

Two

hot-swap

management

module

bays

Module

bays

(on

rear):

v

Four

hot-swap

I/O

module

bays

v

Four

hot-swap

blower

bays

v

One

hot-swap

KVM

(keyboard,

video,

mouse)

module

v

One

hot-swap

LAN

module

Power

modules:

v

Standard:

Two

1300-watt

or

greater

hot-swap

-48

V

dc

(-40

to

-60

V

dc)

power

modules

Power

modules

1

and

2

supply

power

to:

-

Blade

bays

1

through

4

-

Management

modules

1

and

2

-

I/O

modules

1

and

2

-

Media

tray

-

All

KVM,

LAN,

and

alarm

interfaces

-

All

four

blower

modules

Power

modules

1

and

2

provide

redundancy

to

each

other

v

Maximum:

Four

1300-watt

or

greater

hot-swap

-48

V

dc

(-40

to

-60

V

dc)

power

modules

Power

modules

3

and

4

supply

power

to:

-

Blade

bays

5

through

8

-

I/O

modules

3

and

4

Power

modules

3

and

4

provide

redundancy

to

each

other

Blowers

are

powered

by

all

four

power

modules

LAN

module:

v

Two

10/100

Mb

Ethernet

remote

management

connections

v

One

DSUB

15P

alarm

connector

KVM

module:

v

Video

port

(analog)

v

PS/2

keyboard

port

v

PS/2

mouse

port

v

System-status

panel

I/O

modules:

v

Standard:

None

v

Maximum:

Four

Two

hot-swap

1

Gb

Ethernet

four-port

switch

modules

Two

hot-swap

switch

modules

of

another

network-communication

standard,

such

as

Fibre

Channel

Management

module:

v

Standard:

One

hot-swap

management

module

providing

system-management

functions

for

the

BladeCenter

T

unit

v

Maximum:

Two

hot-swap

management

modules

(one

active,

one

redundant)

Redundant

cooling:

Four

variable-speed

hot-swap

blowers

Front

bezel

with

changeable

filter

Upgradeable

microcode:

v

management

module

firmware

v

I/O-module

firmware

(not

all

I/O

module

types)

v

Blade

server

service

processor

firmware

(BIOS,

service

processor)

Size

(8

U):

v

Height:

349.25

mm

(13.75

in.

or

8

U)

v

Depth:

508

mm

(20

in.)

from

front

of

chassis

to

rear

I/O

connector

plane

Maximum

depth:

600

mm

(23.62

in.)

including

bezel,

handles,

and

cable

bend

radius.

v

Width:

442

mm

(17.4

in.)

v

Weight:

Fully

configured

with

modules

and

blade

servers:

Approx.

100.2

kg

(221

lb)

Fully

configured

without

blade

servers:

Approx.

61.7

kg

(136

lb)

Security

features:

v

Login

password

for

remote

connection

v

Lightweight

Directory

Access

Protocol

(LDAP)

and

role

based

security

for

user

authentication

and

authorization

v

Secure

Shell

(SSH)

for

remote

command-line

interface

v

Secure

socket

layer

(SSL)

security

for

remote

Web

interface

access

Predictive

Failure

Analysis

®

(PFA)

alerts:

v

Blowers

v

Blade-dependent

features

v

Power

supplies

Declared

acoustical

noise

emission

levels

for

normal

operations:

v

Sound-power

levels

(upper-limit):

7.8

bels

v

Sound-pressure

levels

(average),

for

four

one-meter

bystander

positions:

63

dBA

The

noise

emission

levels

stated

are

the

declared

upper

limit

sound-power

levels,

in

bels,

for

a

random

sample

of

machines.

All

measurements

made

in

accordance

with

ISO

7779

and

reported

in

conformance

with

ISO

9296.

Environment:

v

Air

temperature:

Altitude:

-60

to

1800

m

(-197

ft

to

6000

ft)

-

BladeCenter

T

on:

to

40°C

(41°

to

104°F)

-

BladeCenter

T

on

(short

term):

-5°

to

55°C

(23°

to

131°F)

Altitude:

1800

m

to

4000

m

(6000

ft

to

13000

ft)

-

BladeCenter

T

on:

to

30°C

(41°

to

86°F)

-

BladeCenter

T

on

(short

term):

-5°

to

45°C

(23°

to

113°F)

System

unit

off:

uncontrolled

v

Rate

of

temperature

change:

30°C/hour

(54°F/hour)

v

Humidity:

BladeCenter

T

on:

5%

to

85%

BladeCenter

T

on

(short

term):

5%

to

90%

not

to

exceed

0.024

water/kg

of

dry

air

BladeCenter

T

off:

uncontrolled

Electrical

input:

v

dc

power

v

Input

voltage:

-48

V

dc

(-38

V

dc

to

-75

V

dc)

v

Input

current:

Chassis:

70

amp

maximum

Single

power-supply

feed:

70

amp

maximum

v

Input

connector

type:

Two

(2)

four

post

DC

terminals,

rated

at

70

amps

each.

Heat

output:

v

Input

kilovolt-amperes

(kVA)

approx.

Minimum

configuration:

0.2

kVA

Maximum

configuration:

3.7

kVA

v

BTU

output

Ship

configuration:

673

Btu/hour

(197

watts)

Full

configuration:

12640

Btu/hour

(3707

watts)

Chapter

1.

General

information

5