Digital Modules

4-35

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Status, Interrupts, Diagnostics

Status display

Green LED per
channel

Interrupts

•

Hardware interrupt

•

Diagnostic Interrupt

Parameters can be
assigned

Parameters can be
assigned

Diagnostic functions

•

Monitoring of the power
supply voltage of the
electronics

Yes

•

Load voltage monitor

Green LED per group

•

Group error display

–

For internal fault

–

For external fault

Red LED (INTF)

Red LED (EXTF)

•

Channel error display (F)

None

•

Diagnostic information can
be displayed

Yes

Monitoring for

•

Wire break

I < 1 mA

Substitute value can be applied

Yes

Sensor Power Supply Outputs

Number of outputs

2

Output voltage

•

with load

Min. L+(–2.5 V)

Output current

•

Rated value

•

Permitted range

120 mA

0 to 150 mA

Additional (redundant) supply

Possible

Short-circuit protection

Yes, electronic

Data for Selecting a Sensor

Input voltage

•

Rated value

•

For signal “1”

•

For signal “0”

24 VDC

11 V to 30 V

-30 V to 5 V

Input current

•

At signal “1”

•

At signal “0”

6 mA to 12 mA

< 6 mA

Input characteristic curve

To IEC 61131;
type 2

Connection of two-wire BEROs

•

Permitted bias current

Possible

Max. 3 mA

Time, Frequency

Internal preparation time

1)

for

•

only status recognition

–

Input delay of the
channel groups
0.05 ms/0.05 ms

max. 50

m

s

–

Input delay of the
channel groups
0.05 ms/0.1 ms or 0.1
ms/0.1 ms

max. 70

m

s

–

Input delay of the
channel groups
>= 0.5 ms

max. 180

m

s

•

Status recognition and
enable process interrupt

–

Input delay of the
channel groups
0.05 ms/0.05 ms

2)

max. 60

m

s

–

Input delay for the
channel groups
0.05 ms/0.1 ms or 0.1
ms/0.1 ms

max. 80

m

s

–

Input delay of the
channel groups
>= 0.5 ms

max. 190

m

s

Internal preparation time for
diagnostics/diagnostic interrupt

Input delay

max. 5 ms

•

Parameters can be
assigned

Yes

•

Rated value

0.1/0.5/3 ms

•

Input frequency
(with a time delay of
0.1 ms)

< 2 kHz

Values go into cycle and response times.

Sensor Circuit

Resistance circuit of the sensor
for wire break monitoring

10 to 18 k

Ω

1) The filter times are added to the overall runtime of the
selected input delay.
2) Substitute functionality; diagnostics and diagnostic
interrupt are not to be selected.