Technical Specifications of the SM 421; DI 32

120 VUC

Dimensions and Weight

Dimensions W

H

D (mm)

25

290

210

Weight

Approx. 600 g

Data for Specific Module

Number of inputs

32

Length of cable

•

Unshielded

•

Shielded

600 m

1000 m

Voltages, Currents, Potentials

Rated load voltage L+

79 to 132 VAC

80 to 132 VDC

•

Reverse polarity protection

Yes

Number of inputs that can be
triggered simultaneously

32

Isolation

•

Between channels and
backplane bus

Yes

•

Between the channels

Yes

–

In groups of

8

Permitted potential difference

•

Between M

internal

and the

inputs

120 VAC

•

Between the inputs of the
different groups

250 VAC

Insulation tested with

1500 VAC

Current consumption

•

From the backplane bus

Max. 0.2 A

Power dissipation of the
module

Typ. 6.5 W

Status, Interrupts, Diagnostics

Status display

Green LED per
channel

Interrupts

None

Diagnostic functions

None

Data for Selecting a Sensor

Input voltage

•

Rated value

•

For signal “1”

•

For signal “0”

120 VUC

79 to 132 VAC

80 VDC to 132 VDC

0 to 20 V

•

Frequency range

47 to 63 Hz

Input current

•

At signal “1”

•

At signal “0”

2 mA to 5 mA

0 to 1 mA

Input delay

•

At “0” to “1”

•

At “1” to “0”

5 to 25 ms

5 to 25 ms

Input characteristic curve

To IEC 61131; type 1

Connection of two-wire BEROs

•

Permitted bias current

Possible

Max.1 mA