Siemens Simatic S7-400 User Manual

Page 510

Advertising
background image

Interface Submodules

13-14

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Table 13-13

Meaning of the Addressing Type Bits in the Configuration Register
(IF 962-COM)

I/O Address

Addressing Type COM b/a

I/O Address

Bit 6/2

Bit 5/1

Bit 4/0

Addressing only possible in the reserved I/O address area

(from C000

H

) (default)

0

0

0

280

H

0

0

1

2E8

H

0

1

0

2F8

H

0

1

1

380

H

1

0

0

3E8

H

1

0

1

3F8

H

1

1

0

0

1

1

1

Note

The AT-compatible I/O address can only be set once for each COM port of an
automation computer (including those permanently installed in a programmable
module).

COM Ports

The COM ports (COMa and COMb) of the UART 16C552 can be addressed from
offset addresses 10

H

or 18

H

in accordance with component specification 16C552.

Data Formats

The following data formats can be set in the IF 962-COM interface submodule:

Data bits:

5 bits, 6 bits, 7 bits, 8 bits

Parity:

Even, odd, disable

Stop bit:

1 bit, 1.5 bits, 2 bits

Transmission Speed

The following transmission speeds (transmission rates) can be set in the
IF962-COM interface submodule:

AT-compatible transmission speeds and transmission speeds up to 115.2 Kbps.

Note

Please note that a safe level of transmission speed depends on factors such as
cable length, cable type, and environmental interference.

Advertising
This manual is related to the following products: