Analog Modules

5-113

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Status, Interrupts, Diagnostics

Interrupts

•

Hardware interrupt

Parameters can be
assigned

•

Hardware interrupt when
limit has been exceeded

Parameters can be
assigned

•

Diagnostic Interrupt

Parameters can be
assigned

Diagnostic functions

•

Group error display

–

For internal fault

–

For external fault

Red LED (INTF)

Red LED (EXTF)

•

Diagnostic information
readable

Yes

Substitute value can be applied

No

Data for Selecting a Sensor

Input range (rated values)/Input
resistance

•

Voltage

"

25 mV/1 M

W

"

50 mV/1 M

W

"

80 mV/1 M

W

"

250 mV/1 M

W

"

500 mV/1 M

W

"

1 V/1 M

W

"

2.5 V/1 M

W

"

5 V/1 M

W

1 V to 5 V

/

1 M

W

"

10 V/1 M

W

•

Current

0 mA to 20 mA

/

50

W

"

5 mA/50

W

"

10 mA/50

W

"

20 mA/50

W

4 mA to 20 mA

/

50

W

•

Resistors

0 to 48

W/

1 M

W

0 to 150

W/

1 M

W

0 to 300

W/

1 M

W

0 to 600

W/

1 M

W

0 to 6000

W/

1 M

W

(can be used up to
5000

W

)

•

Thermocouples

TC type B/1 M

W

TC type R/1 M

W

TC type S/1 M

W

TC type T/1 M

W

TC type E/1 M

W

TC type J/1 M

W

TC type K/1 M

W

TC type U/1 M

W

TC type L/1 M

W

TC type N/1 M

W

•

Resistance thermometer

Pt 100/1 M

W

Pt 200/1 M

W

Pt 500/1 M

W

Pt 1000/1 M

W

Ni 100/1 M

W

Ni 1000/1 M

W

Maximum input voltage for
voltage input
(destruction limit)

Max. 18 V continuous;
75 V for 1 ms (cycle
factor 1 : 20)

Maximum input current for
current input (destruction limit)

40 mA

Connection of the signal
sensor

•

For measuring voltage

Possible

•

For measuring current

–

As two-wire
transmitter

Possible

–

As four-wire
transmitter

Possible

•

For measuring resistance

–

With two-conductor
terminal

Possible; cable
resistance is also
measured

–

With three-conductor
terminal

Possible

–

With four-conductor
terminal

Possible

•

Load of the two-wire
transmitter

Max. 750

W

Characteristic linearization

Parameters can be
assigned

•

For thermocouples

Types B, R, S, T, E, J,
K, U, L, N

•

For
resistance thermometer

Pt 100, Pt 200, Pt 500,
Pt 1000, Ni 100,
Ni 1000

Temperature compensation

Yes, programmable

•

Internal temperature
compensation

No

•

External temperature
compensation with
compensating box

Possible

•

External temperature
compensation with Pt 100

Possible

•

Compensation for
definable reference
junction
temperature

Possible

Unit for temperature
measurement

Degrees Celsius