Siemens Simatic S7-400 User Manual

Page 211

Advertising
background image

Digital Modules

4-89

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Technical Specifications of the SM 422; DO 16

20-120 VAC/2 A

Dimensions and Weight

Dimensions W

H

D

(in millimeters)

25

290

210

Weight

Approx. 800 g

Data for Specific Module

Number of outputs

16

Length of cable

•

Unshielded

•

Shielded

Max. 600 m

Max. 1000 m

Voltages, Currents, Potentials

Rated load voltage L+

20 to 132 VAC

•

Permitted frequency range

47 Hz to 63 Hz

Total current of the outputs

Up to 40

_

C

Up to 60

_

C

With fan subassembly

Max. 16 A

24 A

Max. 7 A

16 A

Isolation

•

Between channels and
backplane bus

Yes

•

Between the channels

In groups of

Yes

1

Permitted potential difference

•

Between M

internal

and the

outputs

120 VAC

•

Between the outputs of the
different groups

250 VAC

Insulation tested with

1500 VDC

Current consumption

•

From the backplane bus

•

From load voltage L +
(without load)

Max. 600 mA

Max. 0 mA

Power dissipation of the
module

Typ. 20 W

Status, Interrupts, Diagnostics

Status display

Green LED per
channel

Interrupts

•

Diagnostic Interrupt

Parameters can be
assigned

Diagnostic functions

Parameters can be
assigned

•

Group error display

–

For internal fault

Red LED (INTF)

–

For external fault

Red LED (EXTF)

•

Diagnostic
information readable

Possible

Substitute value can be applied

Yes, programmable

Data for Selecting an Actuator

Output voltage

•

At signal “1”

L1 (–1.5 Vrms)

Output current

•

At signal “1”

Rated value

Permitted range

2 A

100 mA to 2 A

Permitted surge current
(per group)

Max. 20 A/2 cycles

•

At signal “0” (leakage
current)

Max. 2.5 mA at 30 V

Max. 4.5 mA at 132 V

Output delay (for resistive load)

•

From “ 0” to “1”

1 ms

•

At “1” to “0”

1 AC cycle

Zero cross inhibit voltage

Non-zero cross outputs

Size of the motor starter

Max. size 5 to NEMA

Lamp load

Max. 50 W

Parallel connection of 2
outputs

•

For redundant triggering of
a load

Possible (only outputs
of the same group)

•

To increase performance

Not possible

Triggering a digital input

Possible

Switch rate

•

For resistive load

Max. 10 Hz

•

For inductive load
to IEC 947-5-1, DC 13

Max. 0.5 Hz

•

For lamp load

1 Hz

Short-circuit protection of the
output

•

Min. current required for
fuse to blow

Fuse 8A/125 V 2AG
(per output)

Min. 40 A

•

Max. response time

Typ. 33 ms

Replacement fuses

•

Littelfuse

Fuse, 8 A, quick-acting

225.008

Advertising