Digital Modules

4-46

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Technical Specifications of the SM 421; DI 16

24/60 VUC

Programming package

Associated programming
package

As of STEP 7 V 2.0

Dimensions and Weight

Dimensions W H

D

(in millimeters)

25

290

210

Weight

Approx. 600 g

Data for Specific Module

Number of inputs

16

Length of cable

•

Unshielded
input delay

–

0.5 ms

–

3 ms

–

10 / 20 ms

Max. 100 m
Max. 600 m
Max. 600 m

•

Shielded line length

1000 m

Voltages, Currents, Potentials

Number of inputs that can be
triggered simultaneously

16

Isolation

•

Between channels and
backplane bus

Yes

•

Between the channels

Yes

–

In groups of

1

Permitted potential difference

•

Between the different
circuits

75 VDC, 60 VAC

Insulation tested with

•

Channels against
backplane bus and load
voltage L+

1500 VAC

•

Channels among one
another

1500 VAC

Current consumption

•

From the backplane bus

Max.150 mA

Power dissipation of the
module

Typ. 8 W

Status, Interrupts, Diagnostics

Status display

Green LED per
channel

Interrupts

•

Hardware interrupt

•

Diagnostic Interrupt

Parameters can be
assigned
Parameters can be
assigned

Diagnostic functions

Parameters can be
assigned

•

Group error display

–

For internal fault

Red LED (INTF)

–

For external fault

Red LED (EXTF)

•

Channel error display (F)

None

•

Diagnostic information can
be displayed

Possible

Monitoring for

•

Wire break

I > 0.7 mA

Substitute value can be applied

No

Sensor Selection Data

Input voltage

•

Rated value

24 VUC to 60 VUC

•

For signal “1”

15 to 72 VDC
-15 VDC to -72 VDC
15 to 60 VAC

•

For signal “0”

-6 VDC to +6 VDC
0 VAC to 5 VAC

Frequency range

47 DC/AC to 63 Hz

Input current

•

At signal “1”

Typ. 4 mA to 10 mA

Input characteristic curve

Similar to IEC 61131

1)

Connection of two-wire BEROs

•

Permitted bias current

Possible
Max. 0.5 mA to 2 mA

2)

Time, Frequency

Internal preparation time for

•

Only hardware interrupt
enable

Max. 450

m

s

•

Enable hardware and
diagnostic interrupts

Max. 2 ms

Input delay

•

Parameters can be
assigned

Yes

•

Rated value

0.5/3/10/20 ms

Values go into cycle and response times.

Sensor Circuit

Resistance circuit of the sensor
for wire break monitoring

•

Rated voltage 24 V
(15 V to 35 V)

•

Rated voltage 48 V
(30 V to 60 V)

•

Rated voltage 60 V
(50 V to 72V)

18 k

Ω

39 k

Ω

56 k

Ω

1

) IEC 61131 does not specify any data for UC

modules. The values have been adapted as much
as possible to IEC 61131.

2)

Minimum closed-circuit current is required for wire
break monitoring.