background image

Digital Modules

4-75

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Technical Specifications of the SM 422; DO 32

24 VDC/0.5 A

Dimensions and Weight

Dimensions W

H

D

(in millimeters)

25

290

210

Weight

Approx. 600 g

Data for Specific Module

Number of outputs

32

Length of cable

•

Unshielded

•

Shielded

600 m

1000 m

Voltages, Currents, Potentials

Power rated voltage of the
electronics L+

24 VDC

Rated load voltage L+

24 VDC

Total current of the outputs (per
group)

Up to 40

_

C

Up to 60

_

C

Max. 4 A

Max. 2 A

Isolation

•

Between channels and
backplane bus

Yes

•

Between the channels

In groups of

Yes

8

Permitted potential difference

•

Between the different
circuits

75 VDC, 60 VAC

Insulation tested with

•

Channels against
backplane bus and load
voltage L+

500 VDC

•

Between the outputs of the
different groups

500 VDC

Current consumption

•

From the backplane bus

•

Power supply and load
voltage L+ (no load)

Max. 200 mA

Max. 120 mA

Power dissipation of the
module

Typ. 8 W

Status, Interrupts, Diagnostics

Status display

Green LED per
channel

Interrupts

•

Diagnostic Interrupt

•

Hardware interrupt

Parameters can be
assigned

Parameters can be
assigned

Diagnostic functions

•

Monitoring of the load
voltage

Yes

•

Group error display

–

For internal fault

Red LED (INTF)

–

For external fault

Red LED (EXTF)

•

Diagnostic information
readable

Yes

Monitoring for

•

Short circuit

> 1 A (typ.)

•

Wire break

< 0.15 mA

Substitute value can be applied

Yes

Data for Selecting an Actuator

Output voltage

•

At signal “1”

Min. L + (– 0.8 V)

Output current

•

At signal “1”

Rated value

Permitted range

0.5 A

5 mA to 0.6 A

•

At signal “0” (leakage
current)

Max. 0.5 mA

Load resistor range

48

W

to 4 k

W

Parallel connection of 2
outputs

•

For redundant triggering of
a load

Possible (only outputs
of the same group)

•

To increase performance

Possible (only outputs
of the same group)

Triggering a digital input

Possible

Switch rate

•

For resistive load

Max. 100 Hz

•

For inductive load
to IEC 947-5-1, DC 13

Max. 2 Hz

•

For lamp load

Max. 2 Hz

Limit (internal) of the inductive
circuit interruption voltage up to

Typ. L + (– 45 V)

Short-circuit protection of the
output

•

Threshold on

Electronically cyclic

Typ. 0.75 A to 1.5 A