Siemens Simatic S7-400 User Manual

Page 297

Advertising
background image

Analog Modules

5-81

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Basic error (operational limit at 25

°

C, referred to input

range)

•

Voltage input

–

"

80 mV

–

"

250 mV

–

"

500 mV

–

"

1 V

–

"

2.5 V

–

"

5 V

–

1 V to 5 V

–

"

10 V

"

0.17%

"

0.15%

"

0.15%

"

0.15%

"

0.15%

"

0.15%

"

0.15%

"

0.15%

•

Current input

–

0 mA to 20 mA

–

"

20 mA

–

4 ... 20 mA

"

0.15%

"

0.15%

"

0.15%

•

Resistance test

–

0 to 48

W

;

four-conductor
measurement

"

0.15%

–

0 to 150

W,

four-conductor
measurement

"

0.15%

–

0 to 300

W,

four-conductor
measurement

"

0.15%

–

0 to 600

W;

four-conductor
measurement

"

0.15%

–

0 to 5000

W;

four-conductor
measurement (in
the range of
6000

W

)

"

0.15%

–

0 to 300

W;

three-conductor
measurement

"

0.3%

–

0 to 600

W;

three-conductor
measurement

"

0.3%

–

0 to 5000

Ω;

three-conductor
measurement (in
the range of
6000

W

)

"

0.3%

•

Thermocouples

–

TC type B

–

TC type R

–

TC type S

–

TC type T

–

TC type E

–

TC type J

–

TC type K

–

TC type U

–

TC type L

–

TC type N

"

8.2 K

"

5.2 K

"

5.9 K

"

1.2 K

"

1.8 K

"

2.3 K

"

3.4 K

"

1.8 K

"

2.3 K

"

2.9 K

•

Resistance thermocouples, four-conductor
standard measuring range

–

Pt 100

–

Pt 200

–

Pt 500

–

Pt 1000

–

Ni 100

–

Ni 1000

"

2.0 K

"

2.5 K

"

2.0 K

"

1.6 K

"

0.4 K

"

0.4 K

Climatic measuring range

–

Pt 100

–

Pt 200

–

Pt 500

–

Pt 1000

–

Ni 100

–

Ni 1000

"

0.2 K

"

0.2 K

"

0.2 K

"

0.2 K

"

0.4 K

"

0.4 K

•

Resistance thermocouples, three-conductor
standard measuring range

–

Pt 100

–

Pt 200

–

Pt 500

–

Pt 1000

–

Ni 100

–

Ni 1000

"

3.1 K

"

4.9 K

"

3.9 K

"

3.1 K

"

0.8 K

"

0.8 K

Climatic measuring range

–

Pt 100

–

Pt 200

–

Pt 500

–

Pt 1000

–

Ni 100

–

Ni 1000

"

0.4 K

"

0.4 K

"

0.4 K

"

0.4 K

"

0.8 K

"

0.8 K

Temperature error (with
reference to the input range)

"

0.004% K

Linearity error (with reference
to the input range)

"

0.01% K

Repeat accuracy (in the steady
state at 25

°

C, referred to the

input range)

"

0.1%