Analog Modules

5-143

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Technical Specifications of the SM 432; AO 8 x 13 Bit

Programming package

Associated programming
package

As of STEP 7 V 2.0

Dimensions and Weight

Dimensions W

H

D

(in millimeters)

25

290

210

Weight

Approx. 650 g

Data for Specific Module

Number of outputs

8

Length of cable

•

Shielded

Max. 200 m

Voltages, Currents, Potentials

Supply voltage of the
electronics L+

24 VDC

Rated load voltage L+

24 VDC

•

Reverse polarity protection

Yes

Isolation

•

Between channels and
backplane bus

•

Between the channels

•

Between channels and
load voltage L+

Yes

No

Yes

Permitted potential difference

•

Between the outputs (E

CM

)

•

Between S– and M

ANA

(U

CM

)

•

Between M

ANA

and

M

internal

(U

ISO

)

3 VDC

3 VDC

75 VDC/60 VAC

Insulation tested

•

Between bus and L+/M

•

Between bus and analog
section

•

Between bus and chassis
ground

•

Between analog section
and L+/M

•

Between analog section
and chassis ground

•

Between L+/M and chassis
ground

2120 VDC

2120 VDC

500 VDC

707 VDC

2120 VDC

2120 VDC

Current consumption

•

From the backplane bus

Max. 150 mA

•

Power supply and load
voltage L+ (with rated load)

Max. 400 mA

•

Power supply and load
voltage L+ (no load)

Max. 200 mA

Power dissipation of the
module

Typ. max. 9 W

Analog Value Generation

Resolution including sign

13 bits

Conversion time (per channel)

•

In the ranges 1 V to 5 V
and 4 mA to 20 mA

420

m

s

•

In all ranges

300

m

s

Basic response time of module
(all channels enabled)

•

In the ranges 1 V to 5 V
and 4 mA to 20 mA

3.36 ms

•

In all the other ranges

2.4 ms

Settling time

•

For resistive load

•

For capacitive load

•

For inductive load

0.1 ms

3.5 ms

0.5 ms

Suppression of Interference, Limits of Error

Interference voltage suppression for f = n

(f1

"

1%),

(f1 = interference frequency) n= 1.2 ...

•

Common-mode
interference
(U

CM

< AC 3 V

ss

/50 Hz)

>60 dB

Crosstalk between the outputs

> 40 dB

Operational limit (in the entire temperature range, with
reference to the output range)

•

Voltage outputs

–

"

10 V

–

0 V to 10 V

–

1 V to 5 V

"

0.5 %

"

0.5 %

"

0.5 %

•

Current outputs

–

"

20 mA

–

4 mV to 20 mV

"

1%

"

1%

Basic error (operational limit at 25

°

C, referred to the

output range)

•

Voltage outputs

–

"

10 V

–

0 V to 10 V

–

1 V to 5 V

"

0.5%

"

0.5%

"

0.5%

•

Current outputs

–

"

20 mA

–

0 mA to 20 mA

"

0.5%

"

0.5%

Temperature error (with
reference to the output range)

"

0.02% K

Linearity error (with reference
to the output range)

"

0.05%