Digital Modules

4-67

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Technical Specifications of the SM 422; DO 16

20-125 VDC/1.5 A

Dimensions and Weight

Dimensions W

H

D

(in millimeters)

25

290

210

Weight

Approx. 800 g

Data for Specific Module

Number of outputs

16

Length of cable

•

Unshielded

•

Shielded

Max. 600 m

Max. 1000 m

Voltages, Currents, Potentials

Rated load voltage L1

•

Reverse polarity protection

20 VDC to 138 VDC

Yes, with fuse

Total current of the outputs

1)

Up to 40

_

C

Up to 60

_

C

With fan subassembly
Max. 16 A 21 A

Max. 8 A

14 A

Isolation

•

Between channels and
backplane bus

Yes

•

Between the channels

In groups of

Yes

8

Permitted potential difference

•

Between the outputs of the
different groups

250 VAC

Insulation tested with

1500 VAC

Current consumption

•

From the backplane bus

•

From load voltage L +
(without load)

Max. 700 mA

Max. 2 mA

Power dissipation of the
module

Typ. 10 W

Status, Interrupts, Diagnostics

Status display

Green LED per
channel

Interrupts

•

Diagnostic Interrupt

Parameters can be
assigned

Diagnostic functions

Parameters can be
assigned

•

Group error display

–

For internal fault

Red LED (INTF)

–

For external fault

Red LED (EXTF)

•

Diagnostic information
readable

Yes

Substitute value can be applied

Yes, programmable

Data for Selecting an Actuator

Output voltage

•

At signal “1”

Min. L+ (–1,0 V)

Output current

•

At signal “1”

Rated value

1.5 A

Permitted range

10 mA to 1.5 A

Permitted surge current

Max. 3 A
(for 10 ms)

•

At signal “0” (leakage
current)

Max. 0.5 mA

Output delay (for resistive load)

•

From “ 0” to “1”

Max. 2 ms

•

At “1” to “0”

Max. 13 ms

Parallel connection of 2
outputs

•

For redundant triggering of
a load

Possible (only outputs
of the same group)

•

To increase performance

Possible (only outputs
of the same group)

Triggering a digital input

Possible

Switch rate

•

For resistive load

Max. 10 Hz

•

For inductive load
to IEC 947-5-1, DC 13

Max. 0.5 Hz

Short-circuit protection
of output

Electronically
protected

2)

•

Threshold on

Typ. 04 A to 5 A

Replacement fuses

Fuse, 8 A/250 V, quick
blow

1) To achieve maximum performance capability,

distribute the high-current load between the two
groups.

2) To reset a deactivated output,

first set the output signal to 0 and then to 1.

If output signal 1 is written to a deactivated
output and the short circuit remains, additional
interrupts are generated (provided the diagnostic
interrupt parameter was set).