Siemens Simatic S7-400 User Manual

Page 350

Advertising
background image

Analog Modules

5-134

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Operational limit (in the entire temperature range, with
reference to the input range)

•

Voltage input

"

0.3 %

•

Current input

"

0.5 %

•

Thermocouple

Type B

"

3.5

_

C

Type N

"

2.7

_

C

Type E

"

1.8

_

C

Type R

"

3.3

_

C

Type S

"

3.2

_

C

Type J

"

2.4

_

C

Type L

"

1.7

_

C

Type T

"

0.8

_

C

Type K

"

2.5

_

C

Type U

"

1.2

_

C

Basic error (operational limit at 25

_

C, referred to input

range)

•

Voltage input

"

0.05 %

•

Current input

"

0.15 %

•

Thermocouple

Type B

"

0.9

_

C

Type N

"

0.7

_

C

Type E

"

0.5

_

C

Type R

"

0.9

_

C

Type S

"

0.8

_

C

Type J

"

0.6

_

C

Type L

"

0.4

_

C

Type T

"

0.2

_

C

Type K

"

0.6

_

C

Type U

"

0.3

_

C

Temperature error (with
reference to the input
range)

"

0.015%/K

Linearity error (with
reference to the input
range)

"

0.15%

Repeatability (in steady
state at 25

_

C, with

reference to the input
range)

"

0.15%

Status, Interrupts, Diagnostics

Interrupts

•

Hardware interrupt

Parameters can be
assigned

•

Diagnostic Interrupt

Programmable

Diagnostic functions

Programmable

•

Group error display

–

For internal fault

–

For external fault

Programmable

Red LED (INTF)

Red LED (EXTF)

•

Diagnostic information
can be displayed

Yes

Data for Selecting a Sensor

Input range (rated
values)/Input resistance

•

Voltage

"

25 mV

"

50 mV

"

80 mV

"

100 mV

"

250 mV

"

500 mV

"

1 V

"

2.5 V

"

5 V

"

10 V

>2 M

Ω

>2 M

Ω

>2 M

Ω

>2 M

Ω

>2 M

Ω

>2 M

Ω

>2 M

Ω

>2 M

Ω

>2 M

Ω

>2 M

Ω

•

Current

"

25 mA

/50

Ω

•

Thermocouple

Types B, N,
E, R, S, J, L,
T, K, U

>2 M

Ω

Maximum input voltage for
voltage input (destruction
limit)

35 V continuous;
75 V for max. 1 s
(duty factor 1:20)

Maximum input current for
current input (destruction
limit)

32 mA

Connection of the sensor

•

For measuring voltage

Possible

•

For measuring current

As four-wire transmitter

Possible

Characteristic linearization

•

For thermocouples

Types B, N, E, R, S, J, L,
T, K, U

Temperature compensation

Yes, programmable

•

Internal temperature
compensation

Possible

Unit for temperature
measurement

Degrees Celsius; degrees
Fahrenheit