PROFIBUS DP Master Interface IM 467/IM 467 FO

8-2

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

8.1

PROFIBUS DP Master Interface IM 467/IM 467 FO

Order Numbers

IM 467

6ES7467-5GJ02-0AB0 (RS 485)

IM 467 FO

6ES7467-5FJ00-0AB0 (F0)

Application

PROFIBUS DP, standardized to IEC 61784–1:2002 Ed1 CP 3/1, enables rapid
communication in the field between programmable controllers, PCs and field
devices. Field devices are devices such as: ET 200 distributed I/O devices, drives,
valve terminals, switchgear and many others.

The IM 467/IM 467 FO interface module is meant to be used in an S7-400
programmable controller. It permits the S7-400 to be connected to PROFIBUS DP.

Note

The PROFIBUS DP master interface IM 467 or IM 467 FO is not a
DP master in accordance with DPV 1.

Configuration

•

Configured as for the S7-400

•

Can be operated without a fan

•

A maximum of 4 IM 467/IM 467 FO can be used in the central controller. There
are no slot rules.

•

The IM 467/IM 467 FO and the CP 443-5 Extended cannot be used together.

•

The transmission rate of 9.6 kbps to 12 Mbps can be set in steps using software

•

Configuration and programming are possible via PROFIBUS DP.
You must not, however, change the PROFIBUS DP parameters.

•

IM 467 with 9-pin subminiature D female connector for connection to
PROFIBUS DP (6ES7467-5GJ02-0AB0)

•

IM 467 FO with fiber-optic cable for connection to
PROFIBUS DP (6ES7467-5FJ00-0AB0)