Digital Modules
4-40
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Behavior when the Input Delay Equals 0.1 ms and an Error Occurs
If you have parameterized the following:
•
An input delay of 0.1 ms or 0.05 ms
•
KLV or SV as the response to an error
•
Substitute “1”
In the event of a fault on a channel that has a 1 signal, the following could occur
before the last valid value or the substitute value ”1” is output:
•
An 0 signal may be briefly output
•
If parameterized, a hardware interrupt may be generated