Technical Specifications of the SM 421; DI 16

x

120/230 VUC

Dimensions and Weight

Dimensions W

H

D

(in millimeters)

25

290

210

Weight

Approx. 650 g

Data for Specific Module

Number of inputs

16

Length of cable

•

Unshielded

•

Shielded

600 m

1000 m

Voltages, Currents, Potentials

Power rated voltage of the
electronics L+

None

Number of inputs
that can be triggered
simultaneously

16

Isolation

•

Between channels and
backplane bus

Yes

•

Between the channels

Yes

–

In groups of

4

Permitted potential difference

•

Between M

internal

and the

inputs

250 VAC

•

Between the inputs of the
different groups

500 VAC

Insulation resistance

4000 VAC

Current consumption

•

From the backplane bus

Max. 80 mA

Power dissipation of the
module

Typ. 12 W

Status, Interrupts, Diagnostics

Status display

Green LED per
channel

Interrupts

None

Diagnostic functions

None

Substitute value can be applied

No

Data for Selecting a Sensor

Input voltage

•

Rated value

•

For signal “1”

120/230 VUC

74 to 264 VAC
80 to 264 VDC
–80 to –264 VDC

•

For signal “0”

0 to 40 VAC
–40 to +40 VDC

Frequency range

47 to 63 Hz

Input current

•

At signal ”1” (120 V)

Typ. 10 mA AC
Typ. 1.8 mA DC

•

At signal ”1” (230 V)

Typ. 14 mA AC
Typ. 2 mA DC

•

At signal “0”

0 to 6 mA AC
0 to 2 mA DC

Input delay

•

At “0” to “1”

Max. 20 ms AC
Max. 15 ms DC

•

At “1” to “0”

Max. 30 ms AC
Max. 25 ms DC

Input characteristic curve

To IEC 61131;
type 2

Connection of two-wire BEROs

•

Permitted bias current

Possible

Max. 5 mA AC